CIO
DESCRIPTION
33
integration circuit that provides for direct processing of 50 Hz signal.
Output logical value of the measured signal is LED signalled on the
front panel. Input circuits are protected against short-time over voltage
by suppressors and against the long-time one by a reverse fuse.
Input D.C. voltage of 3-30V
Input A.C. voltage of 3-30V rms
CIO REO
Binary
output
A single relay output. It includes a relay with a single changeover
contact. The changeover contact terminal is separate, common
contact is doubled (marked as C). The LED signals the presence of
the governing signal of the relay.
Maximum constant voltage 230V rms
Maximum constant current 5A rms