11
Modbus interface
7. Set the desired Modbus parameters via the SPA display or the integrated web interface under "En-
gineering > SPA Control Board > Modbus Settings > Gateway".
Setting via SPA display
Data Format
ABCD: big endian
Gateway
Baudrate
19200
Parity
even, 1 stop bit
Slave Address
1
Gateway
Setting via web interface