Concoa 621 3 Series Installation And Operation Instructions For Download Page 14

14

15

2.  Secure the cylinder connection to the cylinder in the following manner:

a.    Do not force.  Tightening the nut onto the cylinder connection should be easy.  If it is not, the connection 

may be wrong for the type of gas being used.  

b.    Left-hand threads are used on some cylinder connections.  A notch in the middle of the hex nut typically 

indicates a left-hand thread.

c.    Gaskets are used on some inlet connections. Be sure the gasket is in good shape.  Do not over-tighten to 

avoid squashing the gasket into the gas line.  Keep extra gaskets on hand.

d.    Never use oil or grease on regulator or cylinder fittings, as it may contaminate pure gases, or create a fire 

hazard.

Installing the Outlet Connection:

The autoswitch system has the outlet connection at the top of the box.  The connection is a 1⁄4” tube connection.  Connect 
tubing to the autoswitch that is compatible with the application and is capable of handling the pressure required.

Pressurizing the system for the first time (non-manifold use):

Before system startup, it is recommended that all systems be pressure tested, leak tested, and purged with an inert gas 
such as nitrogen.  To accomplish this with connections other than a CGA 580, it will be necessary to use an adapter.  
The recommended use of an adapter is for temporary use only, for system start up and checks.  Adapters should never 
be used on a permanent basis.

1.  Wear safety glasses and gloves.
2.  Be sure that both ends of all hoses or pigtails are secured before pressurizing.  Turn the line regulator knob 

counterclockwise until the knob stops turning. 

3.  When first pressurizing, do not stand in front of or contact the switchover system.  Slowly open the cylinder 

valve. Observe the high pressure gauge for a rise in pressure up to full cylinder pressure. 

4.  Keep the hand wheel or wrench on the open cylinder valve at all times, to allow prompt emergency shut-

off.

5.  Inspect all connections for leaks and fix any leaks.  A leak detection solution may be applied to the connections 

(if compatible with the application) which indicates leaks by bubbling.  To further check for leaks, or if the 
leak detection solution can not be used, close the cylinder valve for a period of time (recommended 24 hours), 
and observe the high pressure gauge for a drop in pressure.  If so indicated, recheck the CGA connection and 
all other high-pressure port connections.  Never attempt to fix a leak under pressure.  If leaks are detected, 
depressurize the system and retighten the connection. Begin again at step 3. 

WARNING:

  While CONCOA assembles the autoswitch system components to exacting leak-tight standards, 

the customer should also inspect for any loosening of internal parts that may occur in shipping or installation by 
completing the pressure decay test detailed above.  If all external leaks have been found, corrected, and the system 
still indicates a leak, disassemble the front cover from the autoswitch after removing the eight screws shown below.  
Check for leaks on the system’s fittings as described above.

6.  Slowly turn the line regulator knob clockwise.  This will increase the pressure of the line.  Adjust to the desired 

working pressure and again check for leaks using the methods described above.  See Figure 13.

Summary of Contents for 621 3 Series

Page 1: ...UCTIONS Before Installing or Operating Read and Comply with These Instructions Controls Corporation of America 1501 Harpers Road Virginia Beach VA 23454 To Order Call 1 800 225 0473 or 757 422 8330 Fa...

Page 2: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Page 3: ...witch is equipped with LED status lights to indicate the condition of the gas cylinders A green indicator light signifies a Normal condition while a red light indicates an Alarm Gas cylinder empty con...

Page 4: ...bar working pressure Always observe the following safety practices Store cylinders with valve caps screwed on and cylinders chained to a supporting wall or column Handle cylinders carefully and only...

Page 5: ...appropriate industrial standards for the intended service and must be thoroughly cleaned before using Comply with all safety rules and precautions of the following 1 American National Standards Insti...

Page 6: ...pose of the relief valve is to protect the autoswitch system and its components only Figure 2 If there is pressure sensitive equipment downstream of the autoswitch system it is recommended that an app...

Page 7: ...pproximately 10 inches to the left and right of center 3 Remove the mounting bracket from the rear of the AutoSwitch Console by removing the retaining nuts at the bottom of the mounting bracket Figure...

Page 8: ...around the threads twice Cut off the excess tape and press the end firmly into the threads Installing the inlet connection For Maniflex Manifold system installation System 621 X12X CGA typical manifo...

Page 9: ...ection of the tube fitting just removed into the diaphragm valve as shown in Figure 8 Wrench tighten 5 Thread the 1 4 NPT connection of the diaphragm valve assembly into the starter block as shown in...

Page 10: ...4 NPT connection of the tube fitting just removed into the diaphragm valve as shown in Figure 9 Wrench tighten 5 Thread the 1 4 NPT connection of the diaphragm valve assembly into the tee purge as sh...

Page 11: ...o the street elbow assembly a second wrench must be in place holding the hex on the street elbow assembly Failure to do so may cause the street elbow assembly to loosen System 621 X31X CGA one pigtail...

Page 12: ...12 Figure 10 1 4 FPT Port with one cylinder per side Figure 11 Diaphragm Valve with 1 4 FPT Port shown with one cylinder per side...

Page 13: ...tee purge assembly into the diaphragm valve assembly a second wrench must be in place holding the diaphragm valve Failure to do so may cause the diaphragm valve assembly to loosen 4 Thread the 1 4 NPT...

Page 14: ...ulator knob counterclockwise until the knob stops turning 3 When first pressurizing do not stand in front of or contact the switchover system Slowly open the cylinder valve Observe the high pressure g...

Page 15: ...e to close the cylinder valve and any other valves that connect the cylinder to the system The full replacement cylinder is now the reserve cylinder Note while changing cylinders on one side there wil...

Page 16: ...o adjust the alarm set point The lowering of the alarm set point pressure may cause the alarm not to work properly When adjustments are made check the function of the system With the knob arrow turned...

Page 17: ...is decreasing on both inlet gauges at the same time 1 Make sure the priority valve knob is turned fully to the right or left 2 Observe the inlet pressure It may be necessary to do this during times of...

Page 18: ...product returned to CONCOA for service Please contact a Customer Service Representative at 1 800 225 0473 to receive this number You will be asked to provide 1 Model Number 2 Gas Service 3 Inlet press...

Page 19: ...e other than CONTROLS CORPORATION OF AMERICA or if the equipment has been subject to abuse misuse negligence or accident CONTROLS CORPORATION OF AMERICA s sole and exclusive obligation and Buyer s sol...

Page 20: ...ADI 3199D Certified ISO 9001 Controls Corporation of America 1501 Harpers Road Virginia Beach VA 23454 To Order Call 1 800 225 0473 or 757 422 8330 Fax 757 422 3125 www concoa com...

Reviews: