Concoa 547 Series Installation And Operation Instructions Manual Download Page 4

4

4 .   Before system startup, it is recommended that all systems be pressure tested, leak tested, and purged 

with an inert gas such as nitrogen. To accomplish this with connections other than a CGA 580, it will be nec-

essary to use an adapter. The recommended use of an adapter is for temporary use, for start-up and system 

checks only.  Adapters should never be used on a permanent basis.

GENERAL SAFETY PRACTICES

!

CAUTION

√  Comply with precautions listed in C.G.A. Pamphlet P-1, Safe Handling of Compressed Gases in Contaiers.

√  Consult the cylinder distributor for the proper use of cylinders and for any restrictions on their use (such as 

flow rate and temperature requirements).

√  Store cylinders with valve caps screwed on, and cylinders chained to a supporting wall or column.

√  Handle cylinders carefully and only with valve caps screwed on. The cap will reduce the chance that the 

cylinder valve will break off if the cylinder is accidentally dropped or falls over. The cap also protects the 

cylinder valve from damage to screw threads, which could cause leaky connections.

√  All manifolds used with flammable gases should be provided with approved flashback arrestors to stop any 

burning gas in the pipeline from getting back to the manifold or cylinders.

√  No smoking should be permitted near oxygen, nitrous oxide, any other oxidizer, flammable gases, or 

flammable mixtures, or in areas where cylinders are stored.

√  Never lift gas cylinders with a magnetic lifting device.

√  Never use an open flame when leak testing.

√  

Before disconnecting nearly empty cylinders, always rotate the priority valve 180º so that the arrow on the 

knob is pointing to the in-use (full) side of the switchover.

!

CAUTION

√  Always close all manifold station and cylinder valves on the nearly empty side of the switchover before 

disconnecting the pigtail CGA fitting.

√  Always stand to the side and slowly open the pigtail cylinder connection  nut.

√  Always tighten the CGA on all new cylinders before opening any valves.

√  Always open valves slowly when high-pressure gases are being used.

√  Always be sure that a cylinder contains the correct gas before connecting it to any manifold.

√  Always leak-test any manifold or distribution pipeline before using.

√  Always be sure that the gas in a pipeline is the correct gas for the intended use.

√  Always close all cylinder valves before disconnecting cylinders from a manifold.

√  Always test cylinders to be sure the cylinders are full before connecting to a manifold.

All gas distribution piping systems must meet the appropriate industrial standards for the intended service 

and  must  be  thoroughly  cleaned  before  using.    For  the  United  States,  some  applicable  safety  rules  and 

precautions are listed below:

1. American National Standards Institute Standard Z49.1, Safety in Welding and Cutting, American

Welding Society, 2501 NW Seventh Street, Miami, Florida 33125

2.  N.F.P.A.  Standard  55,  Compressed  Gases  and  Cryogenic  Fluids  Code  N.F.P.A.,  470 Atlantic Avenue, 

Boston, Massachusetts 02210

3.  N.F.P.A. Standard 51B, Cutting and Welding Processes (same address as #2).

4.  CONCOA publication ADE 872, Safety Precautions in Welding and Cutting.

5.  Local Ordinances

6.  O.S.H.A. Standard 29 CFR

7.    C.G.A.  Pamphlet  C-4,  American  National  Standard  Method  of  Marking  Portable  Compressed  Gas 

Containers to Identify the Material Contained.

Summary of Contents for 547 Series

Page 1: ...nd Comply with These Instructions Controls Corporation of America 1501 Harpers Road Virginia Beach VA 23454 To Order Call 1 800 225 0473 or 757 422 8330 Fax 757 422 3125 www concoa com February 2016 A...

Page 2: ...um inlet only With 547 XXX4 models an optional universal voltage remote alarm provides an audible and visual warning that a changeover is about to occur Pressing a button on the front of the remote al...

Page 3: ...conditions and gas service Things to consider before removing the system from the box 1 Know the properties and special handling requirements of the gas being used Many specialty gases are quite dange...

Page 4: ...lways rotate the priority valve 180 so that the arrow on the knob is pointing to the in use full side of the switchover CAUTION Always close all manifold station and cylinder valves on the nearly empt...

Page 5: ...the cylinder decreases Manifolds installed in open locations should be protected from weather conditions During winter protect the manifold from ice and snow In summer shade the manifold and cylinders...

Page 6: ...ad as shown in Figure 3 make sure the tape does not overlap the end of the fitting As the tape is wrapped in the direction of the thread spiral pull tightly on the end of tape so that the tape conform...

Page 7: ...to avoid squashing the gasket into the gas line Keep extra gaskets on hand c Never use oil or grease on regulator or cylinder fittings as it may contaminate pure gases or create a fire hazard Installi...

Page 8: ...X 547 3XXX 547 4XXX Cylinder Pressure 250 350 PSIG 17 24 BAR 1050 1150 PSIG 72 79 BAR 1250 1500 PSIG 86 103 BAR 1800 2300 PSIG 124 159 BAR 2800 3300 PSIG 193 228 BAR 3800 4300 PSIG 262 297 BAR higher...

Page 9: ...ght side switching pressures MAINTENANCE On regular intervals the system should be checked for leaks and proper function see trouble shooting Any leaks in the system should be corrected immediately Th...

Page 10: ...OA Do the following before shipping 1 Adequately package the system If possible package in the original shipping container 2 Ship prepaid 3 Include a statement of the observed deficiency 4 Indicate th...

Page 11: ...obligation and Buyer s sole and exclusive remedy under the above warranties is limited to repairing using new or reconditioned parts or replacing free of charge except for labor if permanently install...

Page 12: ...12 Controls Corporation of America 1501 Harpers Road Virginia Beach VA 23454 To Order Call 1 800 225 0473 or 757 422 8330 Fax 757 422 3125 www concoa com ADI 5470 B Certified ISO 9001...

Reviews: