Revision 1.21
October 2007.
1
CONCEPT
CONCEPT
CONCEPT
CONCEPT
CONCEPT
Small Low Profile Powered Enclosure.
P/N: 995200PE
INSTALLATION MANUAL
Overview
The Small Low Profile Powered Enclosure can be used wherever Battery-backed 12V supplies are required to power Concept
Modules and associated devices such as Detectors, Readers and Auxiliary Devices such as Strobes, Sounders, Locks, etc.
The Box is designed to house the Transformer, Power Supply PCB, 7AH Battery and a single B1, B2 or C size Concept Module.
e.g. 1 Door/2 Door Access Module, Mini Expander, Analogue Module or LAN Isolator. The Power Supply features a high
reliability design that offers unconditional stability, and has been designed and tested for compatibility with Proximity readers.
When used with a 2 Door Access Module or Mini Expander, a single Ribbon cable may be used (P/No: 605050 or 605049) to
connect the Power Supply to the Module. When this option is used with the Mini Expander, Zones 7 and 8 are connected to the
AC Fail and Low Battery alarm outputs of the Power Supply and cannot be used as general purpose Zone Inputs.
Electrical Specifications
Input:
16V AC @ 2.5A.
Output Voltage:
13.8V DC +/-2%, up to 2A.
(From Transformer provided)
Maximum Output Current:
2 Amps.
Switching Frequency:
50 kHz. approx.
Output Ripple:
100mV RMS max. @ Iout = 2A.
Conversion Efficiency:
80%. approx.
Load Regulation:
+/- 100mV @ Iout = 0.1A to 2.0A.
“Low Battery” trigger voltage: 11V DC.
Battery capacity:
12V 7AH Sealed Lead Acid.
Mechanical Specifications
Dimensions:
Length: 252 mm. (Allow 20mm at bottom of case for Mains cable entry)
Width: 358 mm.
Depth: 83 mm.
Weight:
7.2 kg. (Includes mains transformer, battery and cover)
Power Supply PCB dimensions:
95mm X 80mm X 50mm high.
Operating Environment:
0º to 40º Celsius (Ambient)
15% to 85% Relative humidity (non-condensing)
Powered Equipment Box Parts List
- 2A Power Supply PCB assembly and Mains Transformer mounted in Metal enclosure.
- PCB Mounting plate.
-
Installation Manual. (This document)
- Installation Kit containing:
-
2 x 2 Way Plug on Screw Terminals.
-
Battery connection cable. (P/No: 605051)
-
1 x 8 Way Plug on Screw Terminal.
-
1 x 4A Fast Blow fuse. (Spare)
-
Tamper Switch and Metal bracket.
-
1 x 1.0 Amp Slow Blow Mains fuse. (Spare)
-
2 x 6.3mm Tamper switch connectors.
-
15 x PCB Mounting Clips. *
-
1 x 10 way Ribbon cable -20cm. (P/No: 605050) *
-
15 x M3 screws. *
NOTES: 1) * These items not included in installation kit if this product is supplied with a Concept Module already fitted.
2) If the enclosure and Battery are to be installed in any way other than that shown in Diagram 3 on Page 3, the
optional Battery retaining bracket (P/No: 926005) is required.
Designed & manufactured in Australia.
Due to on-going product development this manual is subject to change without notice.
© 2004 - 2005. Inner Range Pty. Ltd.
Part No: 635200PE