All output monitors on the Thermolator can be enabled or dis-
abled permanently through the OM Enable/Disable Menu in
Test Mode.
You need to use this feature if you have replaced the mother-
board, or if dip switches 7 and 8 have been changed erro-
neously. This will enable any required output monitors that
were disabled and give fuse failures.
Enable Test Mode.
Press any key to display the first test menus.
Select the OM Enable/Disable menu.
Press and hold the Setpoint key for 3 seconds to
index to each test menu until the controller indicates
“oS1” in the actual display and the status of the selected
output in the Select display.
Press the Setpoint
s
or
t
key to change the
status.
Each press of the key changes the output status
from ON to OFF or OFF to ON.
Press the Setpoint to select the next output.
Repeat Step 4 to change the status of the output, or press
any key to continue indexing through the outputs.
Save changes and exit the output menu.
Press and hold the Select key for 3 seconds to save
the changes and exit.
TW-1, TW-2
C
ONTROL
D
ISABLING OR
E
NABLING
O
UTPUT
M
ONITORS
UGH025-0504
Thermolator TW Series
M
AINTENANCE
5-9
1
2
3
4
5
6
O
UTPUT
M
ONITOR
S
ELECTION
G
UIDE
MODEL TYPE DI CC IC
OM1 Pump ON ON ON
OM2 Heat ON ON ON
OM3 Cool ON ON ON
OM4 Vent OFF ON OFF
OM5 Purge (TW-2 option only) ON ON OFF
Summary of Contents for Thermolator TW
Page 68: ...Thermolator TW Series UGH025 0504 5 16 MAINTENANCE...
Page 102: ...Thermolator TW Series UGH025 0504 6 34 TROUBLESHOOTING...
Page 105: ...UGH025 0504 Thermolator TW Series APPENDIX B 1 PUMP CURVES...
Page 106: ......
Page 108: ......
Page 114: ...TW 1 CIRCUIT BOARD UGH025 0504 PD 2...
Page 115: ...UGH025 0504 TW 2 CIRCUIT BOARD PD 3...
Page 116: ......