background image

- 6 -

turning it on again, remove the broken components and the ones that cause 

overloading, then replace the fuse.

• 

The 1st, 2nd, 3rd and 4th zones also have a joint potential-free connection 

point that controls the boiler (NO 

-

 COM). 

These connection points clamp 

shut following the heating command of any of the four thermostats, and this 

starts the boiler. 

• 

The

 NO 

COM

,

 Z1-2

,

 Z3-4

,

 Z1-4 

outputs of the zone controller are equipped 

with delay functions, see Section

 5 

for more information.

3. LOCATION OF THE DEVICE

It is reasonable to locate the zone controller near the boiler and/or the manifold 

in a way, so that it is protected from dripping water, dusty and chemically 

aggressive environment, extreme heat and mechanical damage.

4. INSTALLING THE ZONE CONTROLLER AND PUTTING IT  

INTO OPERATION

Attention! 

The  device  must  be  installed  and  connected  by  a  qualified 

professional! Before putting the zone controller into operation make sure that 

neither the zone controller nor the apparatus to be connected to it is connected 

to the 230 V mains voltage. Modifying the device can cause electric shock or 

product failure.

Attention!

 We recommend that you design the heating system you want to 

control with the 

COMPUTHERM

 

Q4Z

 zone controller so that the heating medium 

can circulate in the closed position of all zone valves when a circulating pump 

is switched on. This can be done with a permanently open heating circuit or by 

installing a by-pass valve.

Attention!

 In switched on state 230 V AC voltage appears on the zone outputs, 

the maximum loadability is 2 A (0,5 A inductive). This information should be 

considered at the installation.
The size of the connection points of the 

COMPUTHERM

 

Q4Z

 zone controller 

allow at most 2 or 3 devices to be connected in parallel to any heating zone. 

If more than this is needed for any of the heating zones (e.g. 4 zone valves), 

then the wires of the devices should be joined before they are connected to the 

zone controller.
To install the zone controller, follow these steps:

• 

Detach the rear panel of the device from its front panel by loosening the 

screws at the bottom of the cover. By this, the connection points of the 

Summary of Contents for Q4Z

Page 1: ...Operating Instructions zone controller for controlling 1 to 4 heating zones COMPUTHERM Q4Z...

Page 2: ......

Page 3: ...h other or in case of need all zones can operate at the same time To control more than 4 zones at a time we recommend using 2 or more COMPUTHERM Q4Z zone controllers 1 zone controller needed per 4 zon...

Page 4: ...connection points T1 T2 T3 T4 one for a room thermostat and one for a zone valve pump Z1 Z2 Z3 Z4 The thermostat of the 1st zone T1 controls the zone valve pump of the 1st zone Z1 the thermostat of t...

Page 5: ...reover the four heating zones also have a joint connection point for a zone valve pump Z1 4 If any of the four thermostats T1 T2 T3 and or T4 switches on then beside the 230 V AC voltage appearing at...

Page 6: ...aratus to be connected to it is connected to the 230 V mains voltage Modifying the device can cause electric shock or product failure Attention We recommend that you design the heating system you want...

Page 7: ...ats connection points for power supply fix phase working when the power switch is turned on fuse 15 A connection points controlling the boiler connection points of the heating zones In case of using e...

Page 8: ...lashes with 3 second intervals the LED stops flashing and indicates the current operating mode Automatic Manual Then the working mode can be changed by pressing the A M button again After 10 seconds t...

Page 9: ...of the thermostats the zone valves pumps associated with the thermostat open start and the boiler also starts also taking the Turn on delay function into account see Section 5 By pressing the A M AUTO...

Page 10: ...tchable voltage of the relay that controls the boiler 230 V AC 50 Hz Switchable current of the relay that controls the boiler 8 A 2 A inductive load Duration of activable Turn on delay function 4 minu...

Page 11: ......

Page 12: ...ves EMC 2014 30 EU LVD 2014 35 EU and RoHS 2011 65 EU Copyright 2020 Quantrax Ltd All rights reserved Manufacturer QUANTRAX Ltd H 6726 Szeged F lem le u 34 Hungary Telefon 36 62 424 133 Fax 36 62 424...

Reviews: