Statox 503 Control Module
Issue 10 / 2018 Page
25
of
46
Figure 17: Control Module - alarm relays setting
1.
Enter the menu „ALARM 1 RELAY“ or „ALARM 2 RELAY“ by pushing .
The procedure is identical for both relays.
With the next alarm the new settings will be effective.
2.
Program the alarm threshold with
◄
or
►
. Push and hold
◄
or
►
button for speed mode.
3.
Confirm with Enter.
4.
Select an alarm type with
◄
or
►
.
5.
Confirm with Enter.
6.
Select a Reset-setting (latching or non-latching) with
◄
or
►
.
7.
Confirm with Enter.
8.
Select a relay setting with
◄
or
►
.
9.
Confirm with Enter.
10.
Display „DONE“ for 2 seconds.
11.
The program returns automatically to the main menu.
12.
Push Reset to return to the measuring mode.
!
MEASURING MODE