
23
If the above conditions are met, the protection immediately exports 3J (C7/C8), 4J (C9/C10),
5J (C11/C12), and drives the accident signal relay 11J (C1/C3) (until manual reset, the relay will
not return), The accident light on the panel turns on. The logic block diagram of the action is
shown in 4-18 (high voltage system):
Switch closing
Over frequency protection--
ON
&
LCD display
Emergency signal outlet
Trip outlet
f Over frequency
Protection Value
Ua>5V
35HZ f<65HZ
T Over frequency
Protection delay
Figure 4-18: Logic diagram of over-frequency protection action
4.19 Low frequency load shedding
1
.
RLP20 Low frequency load shedding
-“
ON
”
;
2
.
Phase A voltage Ua>5V
(
High voltage system
);
Phase A voltage Ua >50V
(
Low voltage
system
)
;
3
.
35HZ
≦
f <65HZ
;
4
.
The circuit breaker is closed, that is R1=1;
5
.
Protection device frequency f sampling value
≦
Low-frequency load shedding value
(
Fdz2
)
;
6
.
Duration of meeting the above conditions
≧
Low-frequency load shedding delay
(
Tfzd2
)
;
Meet the above conditions, the protection immediately exports 3J (C7/C8), 4J (C9/C10), 5J
(C11/C12), and drives the accident signal relay 11J (C1/C3) at the same time (the relay will not
return until manual reset), the panel The accident light is on. The logical block diagram of the
action is shown in 4-19:
Switch closing
Low frequency load
shedding--ON
&
LCD display
Emergency signal outlet
Trip outlet
f Low frequency load
shedding Value
Ua>5V
35HZ f<65HZ
T Low frequency load
shedding delay
Figure 4-19: Logic diagram of low-frequency load shedding protection action
4.20 Overvoltage
1
.
RLP21 Overvoltage
-“
ON
”
;
2
.
In line voltage Uab
、
Ubc
、
Uca
,
There are one or more sampled values
≧
Overvoltage value
(
Udz1
)
;
3
.
Duration of meeting the above conditions
≧
Overvoltage delay
(
Tuzd1
)
;
If the above conditions are met, the protection immediately drives outlets 3J (C7/C8), 4J