Mains monitoring relay  CDMR-62     /   Operating instructions 

Page

 11 

CDMR62e_man_A1.doc 

t

 
Line     /    50.00Hz
100V  103V   101V

L1 / L1- L2       L 2 / L 2-L3       L3 / L3-L 1

t

 
Undervoltage U<<

Stage2 K1__4_  

L1 / L1- L2       L 2 / L 2-L3       L3 / L3-L 1

1)  Standard-Menues: 

    LINE MEASURING VALUES

2)   MAIN MENUES   (Example: Undervoltage Stage 2,  U<<):

Menue ID "Line".
If any tripping is active
the function symbol is 
alternate displayed. 

Relay
configuration:
         = star-type
       = delta

      
    

displayed 
line values:
       = star voltages
         = delta voltages

      
    

okay LED (green)
idicates fault-free line system

Any function energized,
Trip delay progressing

Any tripping active 

"M/V" key:
consecutive switching of displayed values 
from         to        and  phase angle 

Scroll up and down
main menues 

Scroll up and down
main menues 

Fig. 4:     FRONT- PANEL DESCRIPTION

             

Press to branch into the
detailed-menue chain
of U<<.

The string "K1__4__" indicates, that K1 and K4 are
assigned to U<<.  If there is no number in the string 
("K______),  the monitoring function is disabled.

Symbol of  the monitoring function

t

 
Trip Voltage   U<<
[1 - 82]         45.5V

L1 / L1- L2       L 2 / L 2-L3       L3 / L3-L 1

3)  DETAILED-MENUES  (Example: Trip Voltage of  Undervoltage Stage 2):

a) normal mode: menue up / down scrolling
b) change mode: (flashing parameter value): 
    increment / decrement parameter value

a) normal mode:   step forward to next menue
b)change mode: (flashing parameter value):
     transfer of the parameter value to non volatile
     data memory, stop flashing

Symbol of  the monitoring function

Parameter value

Setting range

"M/V" key:

Toggle         key function
between "menue scrolling" and 
"parameter increment/decrement"

"ENTER" key

"ENTER" Taste

"M/V" key
(no effect
in this menu)

Return to the standard "Line ...." menue by simultaneously pressing      and        keys. 

"ENTER" key

static:      external Blocking-input closed
flashing:  self-monitoring alarm

 

Summary of Contents for CDMR-62

Page 1: ...mation about the monitoring functions 4 5 Change of setup values 5 Allocation of the message relays to the switch stages and inversing the message function 6 Combination lock 6 Real time clock 7 Event...

Page 2: ...H failure Blocking Input B response time 40ms Vector surge trip delay 60 80 ms Ambient temperature range 20 C to 60 C LCD display contrast 5 C to 50 C Contact data ohm resistive load see Fig 2 Max swi...

Page 3: ...rmation Wire length for connection B less then 3 m Fig 2 LOAD LIMIT CURVE OF THE OUTPUT CONTACTS 0 5 5 50 500 DC OHM RESISTIVE LOAD AC OHM RESISTIVE LOAD L1 L2 L3 L1 L2 L3 N B HP HN CDMR 62 UH L1 L2 L...

Page 4: ...located to it dis play K_____ in main menu Change of the setup values see page 5 Settings for 3 wire or 4 wire grid The star voltages are monitored in the 4 wire grid The triangular voltages are monit...

Page 5: ...ping on Vs in line L3 independent of L2 and L3 4 L1 L2 L3 tripping on Vs in line L1 or L2 or L3 inclusive or 5 L1 L2 tripping on Vs in line L1 and L2 independent of L3 6 L1 L3 tripping on Vs in line L...

Page 6: ...acts on the relays k1 and K4 The lowercase letter for k1 shows that this relay is negated It is energized in the normal state and released in the tripped state The characters mark the positions of th...

Page 7: ...ey 2 Event menu 1 Line Event number Hnn from the first event menu and tripping function 2 Line Measured values at the instant of tripping The entries 00 to 99 can be selected using this menu The flash...

Page 8: ...dditional to self monitoring the K5 can be assigned to any other monitoring function without restriction Use of the measuring voltage as auxiliary voltage A measuring voltage in the range of 70 300 V...

Page 9: ...well as date and time The Informationen menue will be updated in 1 s intervals Read the event memory Select the menu Ereignisspeicher enter the number of events to be listed starting with the newest a...

Page 10: ...p Angle Psy 0 10 4 0 Trip Voltage Asy 1 30 12 0V Trip Delay Psy 0 600 0 10s Trip Delay Asy 0 600 0 10s Ret Delay Psy 0 600 0 10s Ret Delay Asy 0 600 0 20s Output Relay Psy Output Relay Asy Output Rela...

Page 11: ...into the detailed menue chain of U The string K1__4__ indicates that K1 and K4 are assigned to U If there is no number in the string K______ the monitoring function is disabled Symbol of the monitori...

Page 12: ...Trip Delay 0 04 600 s 0 1s s 27 U Return Delay 0 04 600 s 0 1s s 23 25 U Hysteresis 0 20 Un 3 Switch point V 21 U Output relay K1 K5 15 17 U Trip Voltage 1 130 Un 80 Un V 19 U Trip Delay 0 04 600 s 0...

Page 13: ...s 0 12s s 30 f Hysteresis 0 5 00 Hz 0 05 Hz Hz 28 f Output relay K1 K5 57 Vk Trip Angle 1 30 8 58 Vk Trip Logic 0 9 8 L1 L2 L3 61 Vk BlockingTime 1 20 s 5 s s 62 Vk Pulswidth 1 20 s 1 s s 56 Vk Output...

Reviews: