Line Monitoring Relay CDMR-61 / User Manual
Page
13
CDMR61e_man_A1.doc
Par.
No.
Funct. Parameter
Setting
range
Default
setting
Customers
setting value
Dim
43
f<
Trip Frequ
[45 -65] Hz
49.80 Hz
Hz
47
f<
Trip Delay
[0.06 - 60] s
0.12s
s
48
f<
Return Delay
[0.06 - 60] s
0.12s
s
44
f<
Hysteresis
[0.00 – 5.00] Hz
0.05 Hz
Hz
42
f<
Output Relay
K1 ..K5
--
36
f>
Trip Frequ
[45 -65] Hz
51.00 Hz
Hz
40
f>
Trip Delay
[0.06 - 60] s
0.12s
s
41
f>
Return Delay
[0.06 - 60] s
0.12s
s
37
f>
Hysteresis
[0 – 5.00] Hz
0.05 Hz
Hz
35
f>
Output Relay
K1 ..K5
--
29
f>>
Trip Frequ
[45 -65] Hz
52.00 Hz
Hz
33
f>>
Trip Delay
[0.06 - 60] s
0.12s
s
34
f>>
Return Delay
[0.06 - 60] s
0.12s
s
30
f>>
Hysteresis
[0 – 5.00] Hz
0.05 Hz
Hz
28
f>>
Output Relay
K1 ..K5
--
57
Vs>
Trip Angle
[1- 30] °
8 °
°
58
Vs>
Trip Logic
[0 - 9]
8
(L1+L2+L3)
61
Vs>
BlockingTime
[1 - 20] s
5 s
s
62
Vs>
Pulswidth
[1 - 20] s
1 s
s
56
Vs>
Output Relay
K1 ..K5
--
71, 73
Asy
TripVoltage
[1 - 50%] Un
20 % Un
V
75
Asy
Trip Delay
[0.04 - 60] s
0.1s
s
76
Asy
Return Delay
[0.04 - 60] s
0.1s
s
72, 74
Asy
Hysteresis
[0 - 20%] Un
10%
V
70
Asy
Output Relay
K1 ..K5
--
99
Psy
Trip Angle
[1.0 - 10.0] °
4°
°
103
Psy
Trip Delay
[0.04 - 60] s
0.1s
s
104
Psy
Return Delay
[0.04 - 60] s
0.1s
s
100
Psy
Hysteresis
[0 - 5.0] °
1°
°
98
Psy
Output Relay
K1 ..K5
--
77
SEQ
Output Relay
K1 ..K5
--
79 General
Mains
3-
/4-wire
4-wire
78
Negated Relays
K1 ..K5
--
80
Ext. Blocking U,f
0, 1, 2
0
83
U< Trip Logic
on / off [0/1]
off
82
Selfmonitor. ->K5
on / off [0/1]
off
123
Security Code
[ 0 - 999 ]
000