Comnet FDC24NL Installation And Operation Manual Download Page 5

INS_FDC24NL[SFP]_REV–

12/29/11

PAGE 5

INSTALLATION AND OPERATION MANUAL 

FDC24NL[SFP] SERIES

TECH SUPPORT: 1.888.678.9427

Up to 12 unique addresses are possible within a single system. Only contact information from units with the same address is 

exchanged. Multiple units can exist with the same unit address in which case the contacts behave in an OR function so that an input 

from any unit with the same address will trigger its corresponding output on as many units that have a matching address.
Please refer to Figure 12 for example system topologies.

FIGURE 8 – RS-422 DATA PORTS RJ-45 PIN-OUT

The RS-422 RJ-45 data ports are designed to provide simple connection between units using a standard straight-through patch cable.
Connections should be made B to A. The units should always connect to a fiber device or FDC24NLSFP model using Port B.

PIN # Wire Color Connections

Polarity

1

Blue

DATA IN

2

Orange

DATA IN

+

3

Black

DATA OUT

+

4

Red

NC

5

Green

NC

6

Yellow

DATA OUT

7

Brown

NC

8

White

NC

NC = No Connection

PIN # Wire Color Connections

Polarity

1

Blue

DATA OUT

2

Orange

DATA OUT

+

3

Black

DATA IN

+

4

Red

NC

5

Green

NC

6

Yellow

DATA IN

7

Brown

NC

8

White

NC

NC = No Connection

VIEW INSIDE RJ-45 PORT

RJ-45 PORTS

 

 

The ports are located on the rear panel of each unit

RJ-45 BREAK-OUT KIT (SOLD SEPARATELY)

 

Screw Number Corresponds to RJ-45 Port Pin Number

RS-422 B PORT

RS-422 A PORT

FIGURE 9 – ADDRESS SWITCH SETTINGS

The switch is located on the rear panel of each unit

SW # Address

8

UNIT 8

9

UNIT 9

A

UNIT 10

B

UNIT 11

C

UNIT 12

D

Not Used

E

Not Used

F

Not Used

SW # Address

0

Reserved

1

UNIT 1

2

UNIT 2

3

UNIT 3

4

UNIT 4

5

UNIT 5

6

UNIT 6

7

UNIT 7

Summary of Contents for FDC24NL

Page 1: ...kets that are ordered and encoded ensuring extremely robust transmission Packets that are garbled packets out of sequence and transmission bit errors will not cause random changes of state on the cont...

Page 2: ...PE Power Supply Surface Mount 8 15 VDC 5 W Max Rack Mount From Rack NOTE Remove Electrical Connector for Rack Mount Units FIGURE 2 FDC24NL FRONT PANEL FIGURE 3 FDC24NL REAR PANEL FIGURE 1 FDC24NL RS 4...

Page 3: ...HITE STRIPE Power Supply Surface Mount 8 15 VDC 5 W Max Rack Mount From Rack NOTE Remove Electrical Connector for Rack Mount Units FIGURE 5 FDC24NLSFP FRONT PANEL FIGURE 6 FDC24NLSFP REAR PANEL FIGURE...

Page 4: ...inputs from units with the same address FIGURE 7 CONTACT CLOSURE PIN OUT PIN Wire Color Connections Polarity 1 Blue OUT 1 5 9 13 17 21 2 Orange OUT 1 5 9 13 17 21 3 Black OUT 2 6 10 14 18 22 4 Red OUT...

Page 5: ...cable Connections should be made B to A The units should always connect to a fiber device or FDC24NLSFP model using Port B PIN Wire Color Connections Polarity 1 Blue DATA IN 2 Orange DATA IN 3 Black...

Page 6: ...f that contact is currently open ON Contact Closed OFF Contact Open RED Invalid Address Selected No Fiber Connection or No Mating FDC24 Connected OFF Unit Powered Down Unit Powered Down S2 1 Relay 24...

Page 7: ...24 Contacts IN 24 Contacts IN 24 Contacts IN 24 Contacts IN 24 Contacts IN 24 Contacts IN 24 Contacts IN 24 Contacts OUT From Address 1 Right A A A A A A B B B Max 12 Uniquely Address Units B B B Max...

Page 8: ...om Address 1 Left 24 Contacts OUT From Address 1 Left Contact inputs on the left side will be logic OR ed together as both units have the same address e g closing input 1 on either unit will cause rel...

Page 9: ...and slide it into the card guides in the rack until the edge connector at the back of the card seats in the corresponding slot in the rack s connector panel Seating may require thumb pressure on the...