INSTALLATION AND OPERATION MANUAL 

FDC24NL[SFP] Series

24-CHANNEL DUPLEX CONTACT CLOSURE TRANSCEIVER

The ComNet FDC24NL Series contact closure transceiver units provide transmission 
of up to twenty four independent duplex dry switch or relay contact closures using 
a single SFP optical port or any four-wire RS-422 copper circuit. The FDC24NL Series 
supports an integrated field expandable RS-422 data bus allowing up to 12 uniquely 
addressed units to be connected to the bus providing up to 288 unique duplex 
contact closures over a single SFP optical port or RS-422 copper circuit.

The contact closure information is sent in packets that are ordered and encoded, 
ensuring extremely robust transmission. Packets that are garbled, packets out of 
sequence, and transmission bit errors will not cause random changes of state on 
the contact relays. One relay can be optionally re-purposed as a summary fault 
alarm contact and is triggered in the event that the unit loses fiber or RS-422 bus 
communications. The FDC24NL series is offered with non-latching solid state relays. 
Each module incorporates link and individual status indicating LEDs for monitoring 
confirmation of contact closure input and output of each of the twenty four channels. 
Packaged in the exclusive ComNet ComFit housing, these units may be either wall 
or rack-mounted, or may be DIN-rail mounted by the addition of ComNet model 
DINBKT1 or DINBKT4 adaptor plate.

This manual serves the following 

ComNet Model Numbers:

FDC24NL
FDC24NLSFP

Summary of Contents for FDC24NL

Page 1: ...kets that are ordered and encoded ensuring extremely robust transmission Packets that are garbled packets out of sequence and transmission bit errors will not cause random changes of state on the cont...

Page 2: ...PE Power Supply Surface Mount 8 15 VDC 5 W Max Rack Mount From Rack NOTE Remove Electrical Connector for Rack Mount Units FIGURE 2 FDC24NL FRONT PANEL FIGURE 3 FDC24NL REAR PANEL FIGURE 1 FDC24NL RS 4...

Page 3: ...HITE STRIPE Power Supply Surface Mount 8 15 VDC 5 W Max Rack Mount From Rack NOTE Remove Electrical Connector for Rack Mount Units FIGURE 5 FDC24NLSFP FRONT PANEL FIGURE 6 FDC24NLSFP REAR PANEL FIGURE...

Page 4: ...inputs from units with the same address FIGURE 7 CONTACT CLOSURE PIN OUT PIN Wire Color Connections Polarity 1 Blue OUT 1 5 9 13 17 21 2 Orange OUT 1 5 9 13 17 21 3 Black OUT 2 6 10 14 18 22 4 Red OUT...

Page 5: ...cable Connections should be made B to A The units should always connect to a fiber device or FDC24NLSFP model using Port B PIN Wire Color Connections Polarity 1 Blue DATA IN 2 Orange DATA IN 3 Black...

Page 6: ...f that contact is currently open ON Contact Closed OFF Contact Open RED Invalid Address Selected No Fiber Connection or No Mating FDC24 Connected OFF Unit Powered Down Unit Powered Down S2 1 Relay 24...

Page 7: ...24 Contacts IN 24 Contacts IN 24 Contacts IN 24 Contacts IN 24 Contacts IN 24 Contacts IN 24 Contacts IN 24 Contacts OUT From Address 1 Right A A A A A A B B B Max 12 Uniquely Address Units B B B Max...

Page 8: ...om Address 1 Left 24 Contacts OUT From Address 1 Left Contact inputs on the left side will be logic OR ed together as both units have the same address e g closing input 1 on either unit will cause rel...

Page 9: ...and slide it into the card guides in the rack until the edge connector at the back of the card seats in the corresponding slot in the rack s connector panel Seating may require thumb pressure on the...