3 Commissioning
MF0147A0A
Page 29
3.2.4. Mains Power Connection
Before connecting electrical power to the units, the system must be grounded
(earthed) as described in the previous chapter.
The Mains power must be connected to the Mains connector of the unit for operation
of the RU. A power cable is delivered with each RU. The type of power cable
delivered is dependent on the type of power supply in the RU.
The AC power cable is a 3.2 m (10.5 ft) 16 AWG cable with a 4-pin Amphenol C016
series plug on one end to connect to the RU Mains connector. The other end of the
cable is un-terminated with 3 end splices to connect to the AC power source. A 10 m
(33.7 ft) AC power cable (part no. 7573605-00) is also available as an option. The AC
power cable is shown in figure 3-10.
blue
Amphenol 4-Pin
female connector
Protective Cap
3x end splice
brown
yellow / green
B0302ASA
RU Mains
Connector
4
3
2
1
4-Pin Amphenol C016
Series
Pin
Name
Color
1
Phase
Brown
2
Neutral
Blue
3
n.c.
n.c
4
Ground Yellow /
Green
figure 3-10 AC power cable
table 3-3 AC power cable
The standard DC power cable is a 3.2 m (10.5 ft) 13 AWG cable with a 4-pin
Amphenol C016 series plug on one end to connect to the RU Mains connector. The
other end of the cable is un-terminated with 2 end splices to connect to the -48 Vdc
power source. The standard DC power cable is shown in figure 3-11.
black
Amphenol 4-Pin
female connector
Protective Cap
2x end splice
red
B0302ATA
RU Mains
Connector
4
3
2
1
4-Pin Amphenol C016
Series
Pin
Name
Color
1
n.c
n.c
2
–48V
Black
3
0V
Red
4
n.c.
n.c
figure 3-11 DC power cable
table 3-4 DC power cable