4.3
Fiber Hole Plugs
Fiber hole plugs are shipped with the storage panel for use if the module is not to be mounted
directly above or below another similar module. Install the fiber hole plugs in the fiber pass-
through holes in the top and bottom rear corners of the module.
5
USING THE STORAGE PANEL
Each storage panel stores fiber in a unique way and requires a little different method of routing
the cable for storage.
5.1
Using the Storage Deck Panel
To store a length of cable in the storage deck panel, perform the following procedure:
1. Unlatch (or unlock the optional key lock) and open fully the front cover.
2. Slide the designated storage deck to the front of the storage panel.
3. Store the first cable on the left spools (using the appropriate storage method), making sure
that the final turn comes off the inner part of the rear spool as shown in
route the cable to the left rear corner of the deck, and use waxed linen tape to secure the
cable to the inner tie point (i.e., closest to the spools).
4. Next, route the cable toward the front left corner of the storage deck and out into the vertical
cable guide; adjust the cable slack as necessary to ensure that no pinching or binding will
occur when the storage deck is returned to its normal position in the storage panel.
5. Store the second cable on the pair of spools on the right side of the storage deck; when it
exits the spools, route it through the cable guide at the back of the deck. Tie it down at the
outer tie point in the left rear corner and route it into the VCG as in
.
6. Complete a designation label for the stored patch cord and apply label to front edge of
storage deck assembly.
7. Repeat procedure for each patch cord to be stored. Close front cover when complete.
Note:
For storage loops up to seven meters (23 feet) long, use the
“Figure 8”
method
. For longer loops of up to 16 meters (52.5 feet), use the
“oval”
method
shown in
. For convenience, use the pair of spools on the left side of the storage
deck first.
Caution:
Do not kink or make a sharp bend in the patch cord when forming loop. Excessive
bending may damage the optical fiber within the patch cord
.