Option Links
For the purpose of detecting room
occupancy, we are not as concerned
about false alarms as we would be if
this were a security system. In fact,
not
detecting room movement (when
people
are
in the room) would be more
of a problem.
For this reason,
Long Range
and
Short Pulse Count
links should be
fitted. Similarly, having the LED
activate is a benefit.
So for our application, fit all 3 links.
Testing
With the cover fitted, apply power and
wait at least 30 seconds. After this time, if
there is no movement, the LED should go
out. Once this has happened, any
movement should cause a couple of rapid
flickers and the LED should lock on for
about 5 seconds.
Walk around the room and check that your
movement can be reliably detected. If
range seems to be inadequate, check the
position of the PCB in the base. A higher
position lowers the angle of the detection
beam.
Programming your control panel
to recognise the RMS and perform
actions
In CommBox Control System editor, select
Device Options
under the
Handset
menu.
The
Inactivity Timeout
option allows you to
choose the number of minutes after either
the last key is pressed
or
the RMS sensor
detects movement. When that time expires
with no movement detected or key pressed,
the actions you choose under Edit Actions will
occur.
After you have selected the time, click Edit
Actions. You can treat this just like the
programming of any other key.
For more information
Please refer to the control panel’s manual for
more information.
For Support please call:
+61 02 9938 4811