For the purpose of detecting room 
occupancy, we are not as concerned 

about false alarms as we would be if 
this were a security system. In fact, 

not

 detecting room movement (when 

people 

are

 in the room) would be more 

of a problem. 
For this reason, 

Long Range

 and 

Short Pulse Count

 links should be 

fitted. Similarly, having the LED 

activate is a benefit. 

So for our application, fit all 3 links.

Testing

With the cover fitted, apply power and 
wait at least 30 seconds. After this time, if 

there is no movement, the LED should go 
out. Once this has happened, any 

movement should cause a couple of rapid 
flickers and the LED should lock on for 

about 5 seconds.
Walk around the room and check that your 

movement can be reliably detected. If 
range seems to be inadequate, check the 

position of the PCB in the base. A higher 
position lowers the angle of the detection 

beam.

Programming your control panel 
to recognise the RMS and perform 
actions

In CommBox Control System editor, select 

Device Options

 under the 

Handset

 menu.

The 

Inactivity Timeout 

option allows you to 

choose the number of minutes after either 
the last key is pressed 

or

 the RMS sensor 

detects movement. When that time expires 
with no movement detected or key pressed, 

the actions you choose under Edit Actions will 
occur.
After you have selected the time, click Edit 
Actions. You can treat this just like the 

programming of any other key.

For more information

Please refer to the control panel’s manual for 

more information.