6
7.1 Bed No. and Inductor.
- Press the mode button. (“password” will blink on the display window)
- Enter the password (9999). (“Program” will blink on the display window)
- Enter the code (00). (“pr00[0000]” will blink on the display window)
- Use the button to be displayed pr010000]
- Pr02 indicate the bed no., it can be input up to no.32.
- Press the call button from bed to communicate with the master station, CALL>XXXX-XX
will blink on the display window, and then lift up the handset to input the bed no. If press
the remote-control button, it will be displayed as the following.
ID=1 GRP=2 LP=3
- If press “1” button, ADDR>XXXX-XX will blink on the display window, input the number
and press the remote-control button.
- If press “2” button, GROUP>-XX will blink on the display window, input the number and
press the remote-control button.
- If press “3” button, LAMP>-XX will blink on the display window, input the number and
press the remote-control button.
(No.1: Bed no. No.2: Special Group (Surgery, Labour, etc.) No.3: Inductor Group)
8.1 Summary
Describe the method of installation for a proper operation of Nurse call system and
asafety of end user.
8.1.1 The system classify into three parts.
1) Master station and DSS for system operation
2) PCB Board and Control Circuit classified by power function
3) Bed to be installed in a patient room
8.1.2 All wires shall be connected individually.
8.1.3 Each bed can be complied with presence switch, emergency switch, emergency
shower switch and two colored corridor light.
8.1.4 Corridor toilet can be connected up to 16 ea.
8.1.5 Interphone shall be wired by 10 piece and installed up to 90 ea.
8.2 Work Condition
The system consists of the various electronic components, while its installation.
8.2.1 Cable to be connected in mater station shall be installed at a proper place for the
installation work and kept away from the direct rays of the sun.
8. Installation Work
www.safemag.ru
www.safemag.ru