GMT/KLM 125 FUSE PANEL
SETUP AND OPERATION MANUAL
PURPOSE AND APPLIcAbILITy - PAGE 1
Section 1: Purpose and Applicability
The purpose of this document is to detail the installation and operation instructions for the GMT 125 and
KLM 125 Fuse Panel.
1.1 Product Model
This document applies to the following models of the
Comm/net Systems, Inc GMT 125 and KLM 125 Fuse Panel:
PART NUMBER
MODEL DESCRIPTION
OUTPUTS
MONITORING
COLOR
016-1846-10
-48VDC Dual Input KLM 125
Terminal Block
Standard
Black
016-1847-10
-48VDC Dual Input KLM 125
Terminal Block
Meter Module
Black
016-1848-10
-48VDC Dual Input KLM 125
Connectorized
Standard
Black
016-1849-10
-48VDC Dual Input KLM 125
Connectorized
Meter Module
Black
016-1870-10
-48VDC Dual Input GMT 125
Terminal Block
Standard
White
016-1871-10
-48VDC Dual Input GMT 125
Terminal Block
Standard
Black
016-1872-10
-48VDC Dual Input GMT 125
Connectorized
Standard
White
016-1873-10
-48VDC Dual Input GMT 125
Connectorized
Standard
Black
016-1874-10
-48VDC Dual Input GMT 125
Terminal Block
Meter Module
White
016-1875-10
-48VDC Dual Input GMT 125
Terminal Block
Meter Module
Black
016-1876-10
-48VDC Dual Input GMT 125
Connectorized
Meter Module
White
016-1877-10
-48VDC Dual Input GMT 125
Connectorized
Meter Module
Black
Section 2: Theory of Operation
2.1 Introduction
2.1.1 GMT 125
The GMT 125 product family consists of a dual-input 10A/10B GMT fuse position, 1RU panel with optional
connectorized outputs and meter module. GMT fuses are available for this panel in ratings starting with 1/64
ampere up to 20 ampere rating.
2.1.2 KLM 125
The KLM 125 product family consists of a dual-input 4A/4B GMT and 4A/4B KLM fuse position, 1RU panel
with optional connectorized outputs and meter module.
The bus rating is 125 amperes max per bus. GMT fuses are available for this panel in ratings starting with
1/64 ampere up to 15 ampere rating. KLM fuses are available for this panel in ratings starting with 1 ampere up
to 30 ampere rating.
2.2 Features
GMT 125
y
GMT fuse positions: 20; each available up to 20A max
KLM 125
y
GMT fuse positions: 8; each available up to 15A max
y
KLM fuse positions: 8; each available up to 30A max
All Models
y
Rack mounting: 19 in. or 23 in. via reversible rack mount ears
y
Mounting offset: Front-flush, mid-mount forward, mid-mount rearward
y
LED indicators
(panels with standard bezel; Figure 1)
y
Advanced LCD display
(panels with meter module; Figure 2)
y
Alarm Contacts: Form C dry contacts
y
Rear panel modular jack connections for alarm outputs
y
Fuse distribution output terminals: set screw terminals support 10-22 AWG wires terminated with a
narrow ring or spade lug
(0.25 in. max width)
y
Optional positive latching connectorized output connections
Figure 1. Standard Bezel
(GMT 125 Version Shown)
Figure 2. Meter Module
(GMT 125 Version Shown)