GMT/KLM 125 FUSE PANEL
SETUP AND OPERATION MANUAL
PAGE 10 - OPERATION
5.1.3 Calibration and Settings
To enter the Calibration and Settings Menu, press the Select
(Sel)
button. To advance through each item
on the menu, press the Select
(Sel)
button. NOTE: Any changes are not saved until you have advanced
back to the Home Screen.
5.1.3.1 Reset Inventory
For panels with KLM fuse positions, the meter module keeps track of KLM fuse inventory in order to
report fuse status. Any installed KLM fuses are detected and added to the inventory automatically. When
a fuse is removed, however, the inventory must be reset to clear the fuse fail alarm. Press the (+) button
to reset the KLM fuse inventory. The meter will return to the Home Screen immediately, skipping the
calibration screens. Press
Sel
to advance to the next setting.
5.1.3.2 Bus Voltage Offset
A and B bus voltage offset can be adjusted by pressing the (+) or (-) buttons. The measured bus voltage
is shown in hundredths of volts along with the applied offset. Press
Sel
to advance to the next setting.
5.1.3.3 Bus Voltage Gain
A and B bus voltage gain can be adjusted by pressing the (+) or (-) buttons. The measured voltage is
shown in hundredths of volts along with the applied gain. Press
Sel
to advance to the next setting.
5.1.3.4 Bus Current Offset
A and B bus current offset can be adjusted by pressing the (+) or (-) buttons. The measured load is
shown in tenths of amps alng with the applied offset. Press
Sel
to advance to the next setting.
5.1.3.5 Bus Current Gain
A and B bus current gain can be adjusted by pressing the (+) or (-) buttons. The measured load is shown
in tenths of amps along with the applied gain. Press
Sel
to advance to the next setting.
5.1.3.6 Audible Alarm
Audible alarm can be enabled
(EN)
or disabled
(DIS)
by pressing the (+) or (-) buttons. Press
Sel
to return
to the Home Screen. NOTE: The audible alarm is disabled by default.