17
5.3 Operation data setting table
:
DIGIT MEANING
RANGE
DEFAULT
ADJUST (YES/NO)
00
Return water temp. setting (cooling
mode)
8°C
– 28°C
27°C
yes
01
Return water temp. setting (heating
mode)
15°C
– 40°C
27°C
yes
02
Total working time of compressor after
frosting
30
– 90 min
40 min
To be adjusted by
technicians
03
Setting initialization temp. for
defrosting
-30°C
– 0°C
-7°C
To be adjusted by
technicians
04
Temp. of exit defrost under heating
model
2°C
– 30°C
13°C
To be adjusted by
technicians
05
Max. time of defrost under heating
mode
1
– 12 min
8 min
To be adjusted by
technicians
06
Electronic expansion valve mode
0 (manual) /
1 (auto)
1
To be adjusted by
technicians
07
Automatic restarting after power off
0
– 1
1 (record)
To be adjusted by
technicians
08
Mode (cooling only/heat
pump/auxiliary electrical heating/hot
water)
0
– 3
1 (warmtepomp)
To be adjusted by
technicians
09
Heat pump keeps running or stops
after compressor stop for 30s
0 (keeps running) /
1 (stops)
0
To be adjusted by
technicians
A
Auto mode (return water temp.)
8°C
– 60°C
40°C
To be adjusted by
technicians
B
Setting of EEV. (heating mode)
-F(-15°C) ~F (-
15°C)
5°C
To be adjusted by
technicians
C
Electronic expansion valve manual
steps
10 ~ 50
35
To be adjusted by
technicians
D
Setting of EEV. (cooling mode)
-F(-15°C) ~F (-
15°C)
5°C
To be adjusted by
technicians
E
Maximum temperature setting
30°C
– 70°C
40°C
To be adjusted by
technicians
F
DeltaT setting
1°C
– 20°C
2°C
To be adjusted by
technicians
G
Ambient temp. protection(Min.)
-15°C
– 15°C
-10°C
To be adjusted by
technicians
Summary of Contents for PRO+10
Page 15: ...15 ...
Page 20: ...20 7 Wiring diagram Model PRO 5 PRO 7 PRO 10 PRO 13 ...
Page 21: ...21 Model PRO 18 PRO 24 ...
Page 35: ...35 ...
Page 40: ...40 7 Bedradingsdiagram Model PRO 5 PRO 7 PRO 10 PRO 13 ...
Page 41: ...41 Model PRO 18 PRO 24 2 ...