Comfort Stat CP1717 Owner'S Manual Download Page 5

Figure 2 

Ÿ

 Position wallplate on wall and pull existing wires through large opening. Then level for appearance. Mark holes for plastic anchors provided, if your existing holes do 

not line up with those on the wallplate. 

Ÿ

 Drill holes with 3/16” bit and gently tap anchors into the holes until flush with wall. 

Ÿ

 Reposition wallplate to wall, pulling wires through large opening. Insert mounting screws provided into wall anchor and tighten. See Figure 3.

 

Figure 3 

NOTE: 5­ Wire Systems

 

If your thermostat has one wire marked R or Rh (2, 3, or 4­wire system), then leave the jumper wire between the Rh and Rc terminals on the  wallplate. Otherwise, if 

you have separate Rh and Rc wires (5­wire system), then remove the jumper wire between the Rh and Rc terminals.

 

Connect Wires and Mount Thermostat to wallplate 

Ÿ

 Match and connect the labeled wires to the appropriate coded terminal screws on the wallplate. (See Figure 4, 5.) Ignore any wires which may be present, but which 

were note connected to the old thermostat.

 

Figure 4                        Figure 5 

Ÿ

 Refer to the Wiring Diagrams below to be sure your system is wired correctly. 

Ÿ

 If your system is a single stage heat pump and uses an O or B wire, you must move the System Selector switch inside the thermostat to the Heat Pump position. If 

you have a normal furnace or electric system, leave the switch in the Standard position. Refer to the System Selector section on the back for more information on this 

switch. 

Ÿ

 Be sure to tighten the terminal screws securely, otherwise a loose wire could cause operational problems with your system or thermostat. 

Ÿ

 Push excess wire back into the hole to prevent interference when installing the thermostat to the wallplate. 

Ÿ

 Make sure the System Switch is set to OFF, and the Fan Switch is set to AUTO. 

Rh/O 

Rc

/B

Summary of Contents for CP1717

Page 1: ...d automatically cutoff in Cool mode if the temperature drops below 45 F 7 C 3 Compressor Protection This thermostat provides a 4 minute delay after shutting off the compressor before it can be restart...

Page 2: ...or will flash as a reminder to check your system s filter After changing or cleaning the system filter press and hold the Filter key for 3 seconds The display will blink and the counter will be reset...

Page 3: ...alkaline batteries even if you have recently replaced them Next Move the battery out hold any key then place the battery again You will need to reprogram your thermostat and confirm normal operation I...

Page 4: ...erminal on your existing thermostat IGNORE THE COLOR OF THE WIRES since these do not always comply with the standard After labeling wires disconnect them from the existing thermostat Remove existing w...

Page 5: ...wallplate Match and connect the labeled wires to the appropriate coded terminal screws on the wallplate See Figure 4 5 Ignore any wires which may be present but which were note connected to the old th...

Page 6: ...in the HG position If the Fan does not come on within a minute of the thermostat calling for heating change the switch position to HE The system selector has no effect in the cooling mode NOTE HG posi...

Page 7: ...ies Auto Fan Does Not Turn On Properly 1 Move HG HE selector to correct position 1 Check that the function switch is in the correct position HEAT or COOL 2 There may be as much as 4 mintue delay befor...

Page 8: ......

Reviews: