Comfort Glow S39NT Owner'S Operation And Installation Manual Download Page 6

www.desatech.com

111417-01B

6

Unusually tight construction is defined as 
construction where:
a.  walls and ceilings exposed to the out-

side  atmosphere  have  a  continuous 
water  vapor  retarder  with  a  rating  of 
one perm (6 x 10

-11

 kg per pa-sec-m

2

) or 

less with openings gasketed or sealed 
and 

b.  weather stripping has been added on 

openable windows and doors and 

c.  caulking  or  sealants  are  applied  to 

areas  such  as  joints  around  window 
and door frames, between sole plates 
and floors, between wall-ceiling joints, 
between  wall  panels,  at  penetrations 
for plumbing, electrical and gas lines 
and at other openings.

If your home meets all of the three criteria 
above, you must provide additional fresh air. 
See 

Ventilation Air From Outdoors

, page 7. 

If your home does not meet all of the three 
criteria  above,  proceed  to 

Determining 

Fresh-Air Flow For Heater Location

Confined and Unconfined Space

The 

National Fuel Gas Code, ANSI Z223.1/NFPA 

54

  defines  a  confined  space  as  a  space  whose 

volume is less than 50 cubic feet per 1,000 Btu 

per hour (4.8 m

3

 per kw) of the aggregate input 

rating of all appliances installed in that space and 

an unconfined space as a space whose volume is 

not less than 50 cubic feet per 1,000 Btu per hour 

(4.8 m

3

 per kw) of the aggregate input rating of 

all appliances installed in that space. Rooms com-

municating directly with the space in which the 

appliances are installed*, through openings not 

furnished with doors, are considered a part of the 

unconfined space.
* Adjoining  rooms  are  communicating  only  if 

there are doorless passageways or ventilation grills 

between them.

DETERMINING FRESH-AIR FLOW 
FOR HEATER LOCATION

Determining if You Have a Confined or 
Unconfined Space

Use this work sheet to determine if you have a 

confined or unconfined space.

Space:

 Includes the room in which you will install 

heater plus any adjoining rooms with doorless pas-

sageways or ventilation grills between the rooms.

1.  Determine the volume of the space (length x 

width x height).

 

Length x Width x Height =__________cu. ft. 

(volume of space)

 

Example:

  Space  size  20  ft.  (length)  x  16  ft. 

(width) x 8 ft. (ceiling height) = 2,560 cu. ft. 

(volume of space)

 

If  additional  ventilation  to  adjoining  room  is 

supplied with grills or openings, add the volume 

of these rooms to the total volume of the space. 

2.  Multiply the space volume by 20 to determine 

the maximum Btu/Hr the space can support.

 

 __________ (volume of space) x 20 = (Maxi-

mum Btu/Hr the space can support)

 

Example:

 2,560 cu. ft. (volume of space) x 20 = 

51,200 (maximum Btu/Hr the space can support)

3.  Add the Btu/Hr of all fuel burning appliances in 

the space.

 

Vent-free fireplace 

  __________ Btu/Hr

 

Gas water heater* 

  __________ Btu/Hr

 

Gas furnace 

  __________ Btu/Hr

 

Vented gas heater 

  __________ Btu/Hr

 

Gas fireplace logs 

  __________ Btu/Hr

 

Other gas appliances*  + __________ Btu/Hr

 

Total 

= __________ Btu/Hr

 

* Do not include direct-vent gas appliances. Di-

rect-vent draws combustion air from the outdoors 

and vents to the outdoors.

 

Example:

 

Gas water heater 

  __________ Btu/Hr

 

Vent-free fireplace 

+ __________ Btu/Hr

 

Total 

= __________ Btu/Hr

4.  Compare the maximum Btu/Hr the space can 

support with the actual amount of Btu/Hr used.

 

 _________Btu/Hr (maximum the space can support) 

 

 _________ Btu/Hr (actual amount of Btu/Hr used)

 

Example:

  51,200 Btu/Hr (maximum the space 

can support) 

 

 

69,000  Btu/Hr  (actual  amount  of 

Btu/Hr used)

The space in the example is a confined space because 

the actual Btu/Hr used is more than the maximum 

Btu/Hr the space can support. You must provide ad-

ditional fresh air. Your options are as follows:
A.  Rework worksheet, adding the space of an adjoin-

ing room. If the extra space provides an unconfined 

space, remove door to adjoining room or add 

ventilation grills between rooms. See 

Ventilation 

Air From Inside Building, 

page 7.

B.  Vent room directly to the outdoors. See 

Ventila-

tion Air From Outdoors, 

page 7.

C.  Install a lower Btu/Hr fireplace, if lower Btu/Hr 

size makes room unconfined. 

30,000
39,000
69,000

AIR FOR COMBUSTION 

AND VENTILATION

Continued

Summary of Contents for S39NT

Page 1: ...YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s...

Page 2: ...ing plate This appliance is not convert ible for use with other gases Aftermarket Completion of sale not for purpose of resale from the manufacturer State of Massachusetts The installation must be mad...

Page 3: ...ade Gas may be present even though no odor exists Make certain you read and understand all warn ings Keep this manual for reference It is your guide to safe and proper operation of this heater WARNING...

Page 4: ...r or similar products turn heater off If heated the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture 10 This heater needs fresh air vent...

Page 5: ...on struction unless provisions are provided for adequate combus tion and ventilation air Read the following instructions to insure proper fresh air for this and other fuel burning appliances in your h...

Page 6: ...lation grills between the rooms 1 Determine the volume of the space length x width x height Length x Width x Height __________cu ft volume of space Example Space size 20 ft length x 16 ft width x 8 ft...

Page 7: ...Follow the National Fuel Gas Code ANSI Z223 1 NFPA 54 Section 5 3 Air for Combustion and Ventilation for required size of ventilation grills or ducts Figure 2 Ventilation Air from Inside Building Or...

Page 8: ...wall should not be less than 12 inches B Clearances from outermost point of stove top to any combustible back wall should not be less than 6 inches Includes corner installations C Clearances from the...

Page 9: ...upply This heater requires an external regulator not supplied Install the exter nalregulatorbetweentheheater and propane LP supply WARNING Never connect natural gas heater to private non utility gas w...

Page 10: ...N Continued Figure 6 External Regulator With Vent Pointing Down Propane LP Supply Tank External Regulator Vent Pointing Down Figure 5 Gas Regulator Location and Gas Line Access Into Stove Cabinet 6 Mi...

Page 11: ...to gas supply Check reconnected ttings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valve see Figure 8 2 Pressurize supply piping system by either opening...

Page 12: ...ure 11 Make sure log sits at on rebox oor see Figure 11 IMPORTANT Make sure log does not cover any burner ports see Figure 12 INSTALLATION Continued O F F P I L O T O N H I L O Figure 11 Installing On...

Page 13: ...ure 15 6 Disconnect green ground wire from blower housing if connected by removing screw holding wire terminal see Figure 15 7 Remove the two blower mounting brackets from the rear panel by removing t...

Page 14: ...hut off gas heater during the following blower installation 1 Remove 2 screws from rear tabs on top trim Pull trim forward to remove see Figure 13 page 12 2 Remove three screws from under top lip on e...

Page 15: ...m speed control to front tab of blower housing using screw provided see Figure 22 Tighten securely 21 Using the four screws previously removed mount blower assembly to stove by reattach ing blower bra...

Page 16: ...st shock hazard and should be plugged directlyintoaproperlygrounded three prong receptacle OPERATING HEATER FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not fol low these instructions exactl...

Page 17: ...gas Then smell for gas including near the oor If you smell gas STOP Follow B in the safety information column 2 page 16 If you don t smell gas go to the next step 5 Turn control knob counterclockwise...

Page 18: ...TING BURNERS Check pilot ame pattern and burner ame pat terns often PILOT FLAME PATTERN Figure 25 shows a correct pilot ame pattern Figure 26 shows an incorrect pilot ame pattern The incorrect pilot f...

Page 19: ...me center may carry compressed air in a can You can use a vacuum cleaner in the blow position If using com pressed air in a can please follow the directions on the can If you don t follow directions o...

Page 20: ...y lit burners will have delayed ignition heater will not produce speci ed heat propane LP gas supply may be low Youmayfeelyourgaspressureistoolow Ifso con tact your local propane LP or natural gas sup...

Page 21: ...in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct OBSERVED PROBLEM When ignitor button is pressed there is no spark at ODS pilot When igni...

Page 22: ...aintenance page 19 or replace burner ori ce 1 Clean burner see Cleaning and Maintenance page 19 or replace burner ori ce 2 Replace damaged burner 3 Replace gas control 1 Check burner for dirt and debr...

Page 23: ...vapors from furniture polish wax carpet cleaners etc may turn into white powder residue 1 Metal expanding while heat ing or contracting while cooling REMEDY 1 Refer to Air for Combustion and Ventilati...

Page 24: ...logged 1 Gas leak See Warning statement at top of page 2 Control valve defective 1 Foreign matter between con trol valve and burner 2 Gas leak See Warning statement at top of page 1 Excessive line or...

Page 25: ...Street Bowling Green KY 42103 3414 270 846 1199 1 800 654 8534 Fax 1 800 846 0090 franktalk aol com Master Parts Dist 1251 Mound Ave NW Grand Rapids MI 49504 2672 616 791 0505 1 800 446 1446 www nbmc...

Page 26: ...www desatech com 111417 01B 26 ILLUSTRATED PARTS BREAKDOWN MODELS S39PT AND S39NT SHOWN 7 6 9 4 10 3 2 1 14 5 12 11 10 8 13...

Page 27: ...104285 01 ODS Pilot 1 3 098249 01 098249 01 ODS Nut 2 4 107090 03 107090 03 Burner Outlet Tube 1 5 107089 01 107089 01 Inlet Tube 1 6 111124 01 111124 01 Burner Retainer Spring 1 7 099056 17 099056 16...

Page 28: ...www desatech com 111417 01B 28 1 10 4 13 3 2 14 7 16 15 11 18 20 5 6 9 8 17 12 23 21 19 19 26 26 22 22 21 25 24 ILLUSTRATED PARTS BREAKDOWN STOVE BODY FOR MODELS S39PT AND S39NT...

Page 29: ...r Hinge 2 17 099230 02 Shoulder Screw 4 18 107079 01CJ Heat De ector 1 19 102455 12 Louver Small 2 20 102455 13 Louver Large 1 21 Support End Louver 2 22 Support Center Louver 2 23 101514 01 Blower Se...

Page 30: ...TROLLED BLOWER KIT GA3750 Provides better heat distribution Features variable speed control knob THERMOSTATICALLY CONTROLLED BLOWER KIT GA3650TA Not Shown Provides better heat distribution Features va...

Page 31: ...__ ______________________________________________________ ______________________________________________________ ______________________________________________________ ________________________________...

Page 32: ...e damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel diagnostic cost labor transportation and any and all such other costs related to...

Reviews: