background image

5

105683

OWNER’S MANUAL

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between

the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = ____________________ cu. ft. (volume of space)

Example: 

Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) =  2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) 

÷

 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example:

 2560 cu. ft. (volume of space) 

÷

 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

_________________ Btu/Hr

Gas water heater*

_________________ Btu/Hr

Gas furnace

_________________ Btu/Hr

Vented gas heater

_________________ Btu/Hr

Gas heater logs

_________________ Btu/Hr

Other gas appliances* +

_________________ Btu/Hr

Total                            =

_________________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

 51,200 Btu/Hr (maximum the space can support)

56,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining

room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

 WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the 

National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3 or applicable local codes.

AIR FOR
COMBUSTION AND
VENTILATION

Continued

Example:

Gas water heater

30,000

Btu/Hr

Vent-free heater  +

26,000

Btu/Hr

Total                        =

56,000

Btu/Hr

Continued

Summary of Contents for S26NT

Page 1: ...appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s p...

Page 2: ...s ornausea Ifyouhavethesesigns theheater may not be working properly Get fresh air atonce Haveheaterserviced Somepeople are more affected by carbon monoxide than others These include pregnant women pe...

Page 3: ...inner pack 2 Tilt carton so that stove is upright 3 Remove protective side packaging 4 Slide stove out of carton 5 Remove protective plastic wrap 6 Remove screen by lifting and then pull ing forward...

Page 4: ...passagewaysorventila tion grills between them WARNING This heater shall notbeinstalledinaconfinedspace or unusually tight construction unless provisions are provided foradequatecombustionandven tilati...

Page 5: ...combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used _________________ Btu Hr maximum the space can suppo...

Page 6: ...r from Inside Building VENTILATION AIR Ventilation Air From Inside Building Thisfreshairwouldcomefromanadjoining unconfined space When ventilating to an adjoining unconfined space you must pro vide tw...

Page 7: ...floor ceiling and adjoining side and back walls Carefullyfollowtheinstructionsbelow This stove is a freestanding unit designed to set directly on the floor IMPORTANT You must maintain minimum wall an...

Page 8: ...ap traps moisture and contaminants This keeps them from going into heater controls If sediment trap is not installed or is installed wrong heater may not run properly INSTALLATION Continued CONNECTING...

Page 9: ...hutoff valve to gas supply Check reconnected fittings for leaks TestPressuresEqualToorLessThan 1 2 PSIG 1 Close manual shutoff valve see Fig ure 7 2 Pressurize supply piping system by ei ther using co...

Page 10: ...omblower motor if connected see Figure 12 4 Disconnect green ground wire from blower housing if connected by re moving screw holding wire terminal see Figure 12 5 Install one plastic bushing provided...

Page 11: ...next step 5 Turn control knob counterclockwise C clockwise to the PILOT position Press in control knob for five 5 sec onds see Figure 17 Note You may be running this heater for the first time after ho...

Page 12: ...ny comfort level between Hi and Lo The thermostatwillgraduallymodulatetheheat output and flame height from higher to lower settings or pilot in order to maintain the comfort level you select The ideal...

Page 13: ...t every 2 500 hours of operation or every three months Wealsorecommendthatyoukeeptheburner tubeandpilotassemblycleanandfreeofdust and dirt To clean these parts we recommend using compressed air no gre...

Page 14: ...ged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor to base panel of log set Nut is located behind ba...

Page 15: ...ntil air is removed from line Have gas line checked by local natu ral gas company 3 Observe minimum installation clearances see pages 7 through 9 4 Clean burner see Cleaning and Mainte nance page 13 o...

Page 16: ...e just after burner is lit or shut off Heater produces unwanted odors Heater shuts off in use ODS operates Gas odor even when control knob is in OFF position Gas odor during combustion REMEDY 1 This i...

Page 17: ...t Hartsville SC 29550 7704 803 332 0191 Parts Department Cans Unlimited Inc P O Box 645 Taylor SC 29687 0013 All States 803 879 3009 1 800 845 5301 Parts Department Baltimore Electric 1348 Dixwell Ave...

Page 18: ...18 105683 VENT FREE NATURAL GAS PEDESTAL STOVE ILLUSTRATED PARTS BREAKDOWN S26NT 5 7 6 9 13 4 10 3 2 1 14 15 12 11 10 8...

Page 19: ...lot NG 1 3 098249 01 ODS Nut 2 4 105973 01 Burner Outlet Tube 1 5 105737 01 Injector Holder 1 6 102843 01 Burner Clip 1 7 099056 27 Burner Orifice Injector 1 8 101329 25 Gas Control Valve 1 9 L98305 0...

Page 20: ...20 105683 VENT FREE NATURAL GAS PEDESTAL STOVE ILLUSTRATED PARTS BREAKDOWN S26NT 1 4 13 3 2 14 7 16 15 11 18 10 5 6 9 8 17 12...

Page 21: ...tor 1 PARTS AVAILABLE NOT SHOWN 101054 01 Lighting Instructions Plate 1 100563 01 Warning Plate 1 104310 10 Information Video 1 104108 09 Touch Up Paint Kit 12 oz can 1 Thislistcontainsreplaceablepart...

Page 22: ...sedbyimproperinstallation Travel diagnostic cost labor transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner TO THE FULL EXTEN...

Reviews: