background image

12

104332

BLUE FLAME PROPANE/LP HEATER

PILOT

LO

OFF

HI

IGNITOR

LIGHTING

INSTRUCTIONS

1.

STOP! Read the safety information,
page 11, column 3.

2.

Make sure equipment shutoff valve
is fully open.

3.

Turn control knob clockwise 

Clockwise

to the OFF position.

4.

Wait five (5) minutes to clear out any
gas. Then smell for gas, including
near the floor. If you smell gas,
STOP! Follow “B” in the safety in-
formation, page 11, column 3. If you
don’t smell gas, go to the next step.

5.

Turn control knob counterclockwise

C-clockwise

 to the PILOT position.

Press in control knob for five (5) sec-
onds (see Figure 17).

Note:

 You may be running this

heater for the first time after hook-
ing up to gas supply. If so, the con-
trol knob may need to be pressed in
for 30 seconds. This will allow air to
bleed from the gas system.
• If control knob does not pop up

when released, contact a qualified
service person or gas supplier for
repairs.

6.

With control knob pressed in, push
down and release ignitor button. This
will light pilot. The pilot is attached
to the front of burner. The pilot can
be seen through the glass panel. If
needed, keep pressing ignitor button
until pilot lights.

Note:

 If pilot does not stay lit, refer

to  Troubleshooting, pages 14 through
16. Also contact a qualified service
person or gas supplier for repairs.
Until repairs are made, light pilot
with match. To light pilot with match,
see Manual Lighting Procedure
.

Figure 17 - Control Knob In The OFF
Position

Ignitor Button

Control Knob

OPERATING
HEATER

 Continued

Figure 18 - Pilot

 CAUTION: Do not try to adjust

heating levels by using the equip-
ment shutoff valve.

7.

Keep control knob pressed in for 30
seconds after lighting pilot. After 30
seconds, release control knob.

Note:

 If pilot goes out, repeat steps

3 through 7. This heater has a safety
interlock system. Wait one (1) minute
before lighting pilot again.

8.

Turn control knob counterclockwise

C-clockwise

 to desired heating level. The

main burner should light. Set control
knob to any heat level between HI
and LO.

TO TURN OFF GAS TO

APPLIANCE

Shutting Off Heater

1.

Turn control knob clockwise

Clockwise

 to the OFF position.

2.

Turn off all electric power to the ap-
pliance if service is to be performed.

Shutting Off Burner Only (pilot
stays lit)

Turn control knob clockwise 

Clockwise

 to

the PILOT position.

THERMOSTAT

CONTROL

OPERATION

The thermostatic control used on these
models differs from standard thermo-
stats. Standard thermostats simply turn
on and off the burner. The thermostat
used on this heater senses the room tem-
perature. The thermostat adjusts the
amount of gas flow to the burner. This
increases or decreases the burner flame
height. At times the room may exceed the
set temperature. If so, the burner will
shut off. The burner will cycle back on
when room temperature drops below the
set temperature. The control knob can be
set to any heat level between HI and LO.

Note:

 The thermostat sensing bulb mea-

sures the temperature of air near the
heater cabinet. This may not always agree
with room temperature (depending on
housing construction, installation loca-
tion,  room size, open air temperatures,
etc.). Frequent use of your heater will let
you determine your own comfort levels.

MANUAL LIGHTING

PROCEDURE

1.

Remove front panel (see Figure 7,
page 8).

2.

Follow steps 1 through 5 under Light-
ing Instructions
.

3.

With control knob pressed in, strike
match. Hold match to pilot until pi-
lot lights.

4.

Keep control knob pressed in for 30
seconds after lighting pilot. After 30
seconds, release control knob. Now
follow step 8, column 2.

5.

Replace front panel.

Ignitor Electrode

Pilot Burner

Thermocouple

Summary of Contents for CGP20TB

Page 1: ...ence CGP20TB CGP20TLB CGP30TB CGP30TLB 20 000 Btu Hr Thermostat and 30 000 Btu Hr Thermostat Model Heaters WARNING Improper installa tion adjustment alteration ser vice or maintenance can cause injury...

Page 2: ...can be dangerous 4 This heater shall not be installed in a bedroom or bathroom 5 This heater needs fresh outside air ven tilation to run properly This heater has an Oxygen Depletion Sensing ODS safety...

Page 3: ...shipment 3 Check heater for any shipping damage If heater is damaged promptly inform dealer where you bought heater PRODUCT FEATURES SAFETY DEVICE This heater has a pilot with an Oxygen Depletion Sen...

Page 4: ...ing only iftherearedoorlesspassagewaysorventila tion grills between them PROVIDING ADEQUATE VENTILATION The following are excerpts from National Fuel Gas Code NFPA 54 ANS Z223 1 Sec tion5 3 AirforComb...

Page 5: ...include direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used...

Page 6: ...igure 2 Ventilation Air from Inside Building WARNING Rework work sheet adding the space of the adjoining unconfined space The combined spaces must have enough fresh air to supply all appliances in bot...

Page 7: ...N This heater cre ates warm air currents These currents move heat to wall sur faces next to heater Installing heater next to vinyl or cloth wall coverings or operating heater where impurities such as...

Page 8: ...ng bracket to wall in one of two ways 1 Attaching to wall stud 2 Attaching to wall anchor Removing Front Panel Of Heater 1 Remove two screws near bottom cor ners of front panel 2 Liftstraightupongrill...

Page 9: ...l mounting bracket is firmly fastened to wall Figure 9 Folding Anchor INSTALLATION Continued Figure 10 Popping Open Anchor Wings For Thin Walls Stand Out Tab Figure 11 Mounting Heater Onto Mounting Br...

Page 10: ...un properly IMPORTANT Holdpressureregulatorwith wrench when connecting it to gas piping and or fittings CAUTION Never connect heater directly to the propane LP supply This heater requires an external...

Page 11: ...ppliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHATTODOIFYOUSMELLGAS Do not try to light any appliance Do not touch any elec...

Page 12: ...ol knob Note If pilot goes out repeat steps 3 through 7 This heater has a safety interlock system Wait one 1 minute before lighting pilot again 8 Turn control knob counterclockwise C clockwise to desi...

Page 13: ...an WARNING Turn off heater and let cool before cleaning CAUTION You must keep control areas burner and circu lating air passageways of heater clean Inspect these areas of heater before each use Have h...

Page 14: ...d REMEDY 1 Replace ignitor 2 Replace ignitor 3 Reconnect ignitor cable 4 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 5 Tighten nut holding piezo ignitor to heater cabin...

Page 15: ...ound clean burner see Cleaning and Maintenance page 13 2 Replace gas regulator 1 Problem will stop after a few hours of operation 1 Turn control knob to LO position and let warm up for a minute 2 Oper...

Page 16: ...se just after burner is lit or shut off Heater produces unwanted odors Heater shuts off in use ODS operates Gas odor even when control knob is in OFF position Gas odor during combustion Moisture conde...

Page 17: ...may be low When Gas Quality Is Bad pilot will not stay lit burner will produce flames and soot heater will backfire when lit Youmayfeelyourgaspressureistoolowor gas quality is bad If so contact your l...

Page 18: ...ted on the back page of this manual FLOOR MOUNTING STAND 20 000 Btu Hr Models CGP20TLB GA4500L Ivory CGP20TB GA4500 Champagne 30 000 Btu Hr Models CGP30TLB GA4510L Ivory CGP30TB GA4510 Champagne For l...

Page 19: ...ww nbmc com Washer Equipment Co 1715 Main Street Kansas City MO 64108 2195 KS MO AR 816 842 3911 www washerparts com East Coast Energy Products 707 Broadway W Long Branch NJ 07764 1542 732 870 8809 1...

Page 20: ...20 104332 BLUE FLAME PROPANE LP HEATER 11 1 11 2 CGP20TB CGP20TLB CGP30TB CGP30TLB ILLUSTRATED PARTS BREAKDOWN 1 2 3 4 5 6 7 8 9 10 10 11 12 13 14 16 18 19 20 21 22 15 23 24 17 7...

Page 21: ...Cable 1 10 098249 01 098249 01 Nut M5 2 11 103594 04 103594 04 Pilot ODS 1 11 1 098514 01 098514 01 Thermocouple 1 11 2 106842 01 106842 01 Ignitor Electrode 1 12 103446 01 103447 01 Burner 1 13 0993...

Page 22: ...the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper m...

Reviews: