background image

10

104270

PROPANE/LP GAS HEATER

CHECKING GAS
CONNECTIONS

 WARNING: Test all gas pip-

ing and connections for leaks
after installation or servicing.
Correct all leaks at once.

 WARNING: Never use an open

flame to check for a leak. Apply a
mixture of liquid soap and water
to all joints. Bubbles forming
show a leak. Correct all leaks at
once.

 CAUTION: Make sure exter-

nal regulator has been installed
between propane/LP supply and
heater. See guidelines under 

Con-

necting to Gas Supply, page 9.

Pressure Testing Gas Supply
Piping System

Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)

1.

Disconnect appliance with its appliance
main gas valve (control valve) and equip-
ment shutoff valve from gas supply pip-
ing system. Pressures in excess of 1/2 psig
will damage heater regulator.

2.

Cap off open end of gas pipe where
equipment shutoff valve was connected.

3.

Pressurize supply piping system by ei-
ther using compressed air or opening
propane/LP supply tank valve.

4.

Check all joints of gas supply piping
system. Apply mixture of liquid soap
and water to gas joints. Bubbles form-
ing show a leak.

5.

Correct all leaks at once.

6.

Reconnect heater and equipment
shutoff valve to gas supply. Check re-
connected fittings for leaks.

Test Pressures Equal To Or Less Than 1/2
PSIG (3.5 kPa)

1.

Close equipment shutoff valve (see Fig-
ure 14).

2.

Pressurize supply piping system by ei-
ther using compressed air or opening
propane/LP supply tank valve.

3.

Check all joints from propane/LP sup-
ply tank to equipment shutoff valve (see
Figure 15). Apply mixture of liquid
soap and water to gas joints. Bubbles
forming show a leak.

4.

Correct all leaks at once.

Pressure Testing Heater Gas
Connections

1.

Open equipment shutoff valve (see Fig-
ure 14).

2.

Open propane/LP supply tank valve.

3.

Make sure control knob of heater is in
the OFF position.

4.

Check all joints from equipment shutoff
valve to control valve (see Figure 15).
Apply mixture of liquid soap and water to
gas joints. Bubbles forming show a leak.

5.

Correct all leaks at once.

6.

Light heater (see Operating Heater,
pages 10 and 11). Check all other in-
ternal joints for leaks.

7.

Turn off heater (see To Turn Off Gas
To Appliance
, page 11).

8.

Replace front panel.

Figure 14 - Equipment Shutoff Valve

Equipment
Shutoff
Valve

Figure 15 - Checking Gas Joints

Propane/LP
Supply Tank

Control
Valve
Location

Equipment
Shutoff
Valve

OPERATING
HEATER

FOR YOUR SAFETY

READ BEFORE

LIGHTING

A. This appliance has a pilot which must

be lighted by hand. When lighting the
pilot, follow these instructions exactly.

B. BEFORE LIGHTING smell all

around the appliance area for gas. Be
sure to smell next to the floor because
some gas is heavier than air and will
settle on the floor.

WHAT TO DO IF YOU SMELL
GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do

not use any phone in your building.

• Immediately call your gas supplier

from a neighbor’s phone. Follow
the gas supplier’s instructions.

• If you cannot reach your gas sup-

plier, call the fire department.

C. Use only your hand to push in or turn

the gas control knob. Never use tools.
If the knob will not push in or turn
by hand, don’t try to repair it, call a
qualified service technician or gas
supplier. Force or attempted repair
may result in a fire or explosion.

D. Do not use this appliance if any part

has been under water. Immediately
call a qualified service technician to
inspect the appliance and to replace
any part of the control system and
any gas control which has been un-
der water.

 

 WARNING: If you do not fol-

low these instructions exactly, a
fire or explosion may result caus-
ing property damage, personal
injury or loss of life.

INSTALLATION

Continued

ON

POSIT

O

POS

Open

Closed

Summary of Contents for CGP10LA

Page 1: ...and service must be performed by a qualified installer service agency or the gas supplier WARNING Thisisanunvented gas firedheater Itusesair oxy gen from the room in which it is installed Provisions f...

Page 2: ...n Depletion Sensing ODS safety shutoff system The ODS shuts down the heater if not enough fresh air is available See Air for Combustion and Ventilation pages 4 through 6 6 Keep all air openings in the...

Page 3: ...ional Fire Protection Association Inc Batterymarch Park Quincy MA 02269 UNPACKING 1 Remove heater from carton 2 Remove all protective packaging ap plied to heater for shipment 3 Check heater for any s...

Page 4: ...ntilation However in buildings of unusually tight construction you must provide additional fresh air Unusually tight construction is de fined as construction where a walls and ceilings exposed to the...

Page 5: ...fuel burning appliances in the space Vent free heater ______________ Btu Hr Gas water heater ______________ Btu Hr Gas furnace ______________ Btu Hr Vented gas heater ______________ Btu Hr Gas firepl...

Page 6: ...23 1 Section5 3 AirforCombustionand Ventilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermostat controll...

Page 7: ...See Accessory page 16 LOCATING HEATER This heater is designed to be mounted on a wall WARNING Maintainthemini mumclearancesshowninFigure 4 Ifyoucan providegreaterclear ances from floor ceiling and jo...

Page 8: ...igure 8 Tightening Anchors Thin or Thick Wall thick wall shown Solid Wall 1 16 Space Placing Heater On Mounting Screws 1 Locate two keyhole slots on back panel of heater see Figure 9 2 Place large ope...

Page 9: ...rom Installation must include an equipment shutoffvalve groundjointunion andplugged 1 8 NPT tap Locate NPT tap within reach for test gauge hook up NPT tap must be upstream from heater see Figure 13 Pr...

Page 10: ...ply tank valve 3 Make sure control knob of heater is in the OFF position 4 Check all joints from equipment shutoff valve to control valve see Figure 15 Applymixtureofliquidsoapandwaterto gas joints Bu...

Page 11: ...ystem If control knob does not pop up when released contact a qualified service person or gas supplier for repairs 6 With control knob pressed in push down and release ignitor button This will light p...

Page 12: ...ct pilot flame pat tern Figure 19 shows an incorrect pilot flame pattern The incorrect pilot flame is not touching the thermocouple This will cause the thermocouple to cool When the thermocouple cools...

Page 13: ...ere is spark at ODS pilot but no ignition ODS pilot lights but flame goes out when control knob is released REMEDY 1 Replace ignitor 2 Replace ignitor 3 Reconnect ignitor cable 4 Free ignitor cable if...

Page 14: ...a few hours of operation 1 Turn control knob to LOW position and let warm up for a minute 2 Operate burner until air is removed from line Have gas checked by local propane LP gas company 3 Observe mi...

Page 15: ...apors from paint hair spray glues etc See IMPORTANT statement above 2 Low fuel supply 3 Gas leak SeeWarning statement at top of page 1 Not enough fresh air is available 2 Low line pressure 3 ODS pilot...

Page 16: ...st Parts Central or call DESA International s Parts Department at 1 800 972 7879 for referral information When calling DESA International have ready model number of your heater the replacement part nu...

Page 17: ...616 791 8270 www nbmc com Dayton Hardware P O Box 275 North Dayton Station Dayton OH 45404 0275 All States 937 258 3721 OH 1 800 762 3426 Halco Enterprises 208 Carter Drive Unit 21 West Chester PA 19...

Page 18: ...18 104270 PROPANE LP GAS HEATER CGP10LA CGP6LA 12 2 12 1 ILLUSTRATED PARTS LIST 10 12 11 1 2 3 4 5 6 7 9 8 10 13 14 15 17 18 21 22 25 20 24 23 19 26 27 16...

Page 19: ...1 11 098249 01 098249 01 Nut M5 2 12 099059 03 099059 03 ODS Pilot Assembly 1 12 1 098514 01 098514 01 Thermocouple 1 12 2 098594 01 098594 01 Ignitor Electrode 1 13 104263 02 104263 01 Burner 1 14 09...

Page 20: ...apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by i...

Reviews: