background image

8

Safety 

Precautions

Page 8 

7.

Repairs to sealed components

:

1)

During repairs to sealed components, all electrical supplies shall be disconnected from the equipment

 The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure 
   the technician is aware of potentially flammable atmospheres. Ensure that the leak detection 
   equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately 
   sealed or intrinsically safe.

5)

Presence of fire extinguisher

:

If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate

 

fire 

extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher

 

adjacent 

to the charging area.

6)

No ignition sources

:

No person carrying out work in relation to a refrigeration system which involves exposing any pipe
work that contains or has contained flammable refrigerant shall use any sources of ignition in such a

 

manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette

 

smoking, should be kept sufficiently far away from the site of installation, repairing, removing and

 

disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior
to work taking place, the area around the equipment is to be surveyed to make sure that there are no

 

flammable hazards or ignition risks. No Smoking signs shall be displayed.

7)

Ventilated area

:

Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or

 

conducting any hot work. A degree of ventilation shall continue during the period that the work is carried

 

out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into

 

the atmosphere.

8)

Checks to the refrigeration equipment

:

Where electrical components are being changed, they shall be fit for the purpose and to the correct

 

specification. At all times the manufacturer's maintenance and service guidelines shall be followed. If in

 

doubt consult the manufacturer's technical department for assistance. The following checks shall be

 

applied to installations using flammable refrigerants:
The charge size is in accordance with the room size within which the refrigerant containing parts are

 

installed;
The ventilation machinery and outlets are operating adequately and are not obstructed;
If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence

 

of 

refrigerant; Marking 

on

 the equipment continues to be visible and legible. Markings and signs that

 

are 

illegible shall be corrected;
Refrigeration pipe or components are installed in a position where they are unlikely to be exposed
to any substance which may corrode refrigerant containing components, unless the components are

 

constructed of materials which are inherently resistant to  being corroded or are suitably protected

 

against being so corroded.

9)

Checks to electrical devices

:

Repair and maintenance to electrical components shall include initial safety checks and component

 

inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be

 

connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately

 

but 

it is necessary to continue operation, an adequate temporary solution shall be used. This shall be

 

reported 

to the owner of the equipment so all parties are advised.
Initial safety checks shall include:
That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
That there no live electrical components and wiring are exposed while charging, recovering or purging

 

the system; That there is continuity of earth bonding.

Summary of Contents for PS-101D

Page 1: ...www marsdelivers com Owner s Manual Installation Manual Portable Air Conditioner PS 81D PS 101D ...

Page 2: ...Precautions Air Filter Cleaning Troubleshooting Tips Unit Cleaning Store the unit when not in use Preparation Design Notice Energy Rating Information Ambient Temperature Range For Unit Operating Exhaust Hose Installation Choosing The Right Location Tools Needed Accessories Window Installation Kit Installation Troubleshooting Tips 03 11 11 12 12 12 12 13 13 14 16 18 19 19 21 21 21 21 22 ...

Page 3: ...n the nameplate located on unit have a qualified electrician install the proper receptacle Install the unit on a flat sturdy surface Failure to do so could result in damage or excessive noise and vibration The unit must be kept free from obstruction to ensure proper function and to mitigate safety hazards Do not modify the length of the power cord or use an extension cord to power the unit Do not ...

Page 4: ...the appliance Children must be supervised around the unit at all times be applicable for other countries except the European Countries If the supply power cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard Prior to cleaning or other maintenance the appliance must be disconnected from the supply mains Do not remove any...

Page 5: ...ontact a qualified person to carry out repairs If the damaged power supply cord must be replaced with a new power supply cord obtained from the product manufacturer and not repaired Hold the plug by the head of the power plug when taking it out Turn off the product when not in use WARNING for Using R32 R290 Refrigerant Do not use means to accelerate the defrosting process or to clean other than th...

Page 6: ...nce of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants Please follow the instructions carefully to handle install clear andservice the air conditioner to avoid any damage or hazard Flammable Refrigerant R32 is used within the air conditioner When maintaining or disposing of the air conditioner the refrigerant R32 shall...

Page 7: ...e system 2 Work procedure Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being present while the work is being performed 3 General work area All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out Work in confined spaces shall be avoided The area around the workspace shall b...

Page 8: ...lly into the atmosphere 8 Checks to the refrigeration equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to installations using fl...

Page 9: ...e the copper pipe work If a leak is suspected all naked flames shall be removed extinguished If a leakage of refrigerant is found which requires brazing all of the refrigerant shall be recovered from the system or isolated by means of shut off valves in a part of the system remote from the leak Oxygen free nitrogen OFN shall then be purged through the system both before and during the brazing proc...

Page 10: ...ractice that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant It is essential that electrical power is available before the task is commenced 15 Become familiar with the equipment and its operation b Isolate system electrically c Before attempting the procedur...

Page 11: ...tructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants In addition a set of calibrated weighing scales shall be available and in good working order Hoses shall be complete with leak free disconnect couplings and in good condition Before using the recovery machine check that it is in satisfactory working order has been properly maintained...

Page 12: ...ocedure not to the portable air conditioners themselves The energy rating and noise information for this unit is based on the standard installation using and un extended exhaust duct without window slider adapter as shown in the installation section of this manual At the same time the unit must operate on the COOL MODE and HIGH FAN SPEED by remote controller The unit with 10 feet extended exhaust ...

Page 13: ...square footage of the room you want to cool by multiplying the room length by its width You also need to know the air conditioner s BTU British Thermal Unit rating which indicates the amount of heat it can remove from a room A higher Why is the cooling capacity lower on newer models than on older units number means more cooling power for a larger room Be sure you are comparing only newer models to...

Page 14: ...Window Slider A Bolt 1 pc 1 set Unit Adaptor Security Bracket and 2 Screws 1 pc 1 pc Exhaust Hose Drain Hose 1 pc 1 pc Window Slider Adaptor Power Cord Buckle O N O F F T E M P S H O R T C U T T IM E R O N T IM E R O F F M O D E FA N S LE E P S W IN G LE D 1 pc Window Slider B Remote Controller and Battery only for remote control models 2 pc Foam Seal A Adhesive 2 pc Foam Seal B Adhesive 4 set Scr...

Page 15: ...imes it needs to be cut short to meet the window size please take extra care to cut it properly 2 Use bolts to fasten the window sliders once they are adjusted to the Proper length Window slider A Window slider B Bolt Step Two Install the Exhaust hose assembly to the unit Push the Exhaust hose into the airoutlet opening of the unit along the arrow direction ...

Page 16: ... sash and frame as shown Foam seal B Adhesive type shorter Foam seal A Adhesive type Or Or Window slider A Window slider B if required Foam seal C Non adhesive type 3 Cut the non adhesive foam seal C strip to match the width or height of the window Insert the seal between the glass and the window frame to prevent air and insects from getting into the room 2 Insert the window slider assembly into t...

Page 17: ... range or bend the hose Make sure that there is no obstacle of 20 in in order to the exhaust system works properly All the illustrations in this manual are for explanation purpose only Your air conditioner may be slightly different The actual shape shall prevail Or 5 Insert the window slider adaptor into the hole of the window slider ...

Page 18: ...e set temperature while on COOL HEAT or AUTO MODE While on DRY and FAN modes it shows the room temperature Shows Error codes E0 EEPROM error E1 Room temperature sensor error E2 Evaporator temperature sensor error E3 Condenser temperature sensor error on some models E4 Display panel communication error EC Refrigerant leakage detection malfunction on some models Shows protection code P1 Bottom tray ...

Page 19: ...hows AP to indicate you can set wireless connection If connection router is successful within 8 minutes the unit will exit wireless connection mode automatically and the wireless indicator illuminates If connection has failed within 8 minutes the unit exits wireless connection mode automatically After Wireless connection is successful for some models you can press MODE and DOWN buttons at the same...

Page 20: ... end of the hose is down to let the water flow smoothly When the continuous drain hose is not used ensure that the drain plug and knob are installed firmly to prevent leakage Continuous drain hose Remove the drain plug During heating pump mode remove the lower drain plug from the back of the unit install the drain connector 5 8 universal female mender with 3 4 hose locally purchased Carefully move...

Page 21: ...the unit using a damp lint free cloth and mild detergent Dry the unit with a dry lint free cloth Drain the unit s water collection tray according to the instructions in the following section Run the appliance on FAN mode for 12 hours in a warm room to dry it and prevent mold Turn off the appliance and unplug it Clean the air filter according to the instructions in the previous section Reinstall th...

Page 22: ...ician to inspect the unit and top off refrigerant Decrease the set temperature Make sure all windows and doors are closed Double check the cooling area Turn off the unit disconnect the hose check for blockage and reconnect the hose Remove the heat sources if possible The unit is noisy and vibrates too much The unit makes a gurgling sound The ground is not level Place the unit on a flat level surfa...

Page 23: ... warranty begins on the date of shipment from the factory REMEDY PROVIDED BY THE LIMITED EXPRESS WARRANTY The sole remedy under the Limited Warranty is replacement of the defective unit Labor to diagnose and replace the defective unit is not covered by this Limited Express Warranty If for any reason the replacement product is no longer available during the warranty period Comfort Aire shall have t...

Page 24: ... GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQFH DQG FHUWLILFDWLRQ OO SURGXFWV PHHW DSSOLFDEOH UHJXODWLRQV LQ HIIHFW RQ GDWH RI PDQXIDFWXUH KRZHYHU FHUWLILFDWLRQV DUH QRW QHFHVVDULO JUDQWHG IRU WKH OLIH RI D SURGXFW 7KHUHIRUH LW LV WKH UHVSRQVLELOLW RI WKH DSSOLFDQW WR GHWHUPLQH ZKHWKHU D VS...

Reviews: