background image

506842-01

Page 7  of  42

Issue 1132

All gas fired appliances require air for the combustion

process.  If sufficient combustion air is not available, the

furnace or other appliances will operate inefficiently and

unsafely.  Enough air must be provided to meet the needs

of all fuel burning appliances and appliances such as exhaust

fans which force air out of the house.  When fireplaces,

exhaust fans, or clothes dryers are used at the same time

as the furnace, much more air is necessary to ensure proper

combustion and to prevent a downdraft. Insufficient air

causes incomplete combustion which can result in carbon

monoxide.

In addition to providing combustion air, fresh outdoor air

dilutes contaminants in the indoor air.  These contaminants

may include bleaches, adhesives, detergents, solvents and

other contaminants which can corrode furnace components.

The requirements for providing air for combustion and

ventilation depend largely on whether the furnace is installed

in an unconfined or a confined space.

Unconfined Space

An unconfined space is an area such as a basement or

large equipment room with a volume greater than 50 cubic

feet (1.42 m

3

) per 1,000 Btu (.29 kW) per hour of the

combined input rating of all appliances installed in that space.

This space also includes adjacent rooms which are not

separated by a door.  Though an area may appear to be

unconfined, it might be necessary to bring in outdoor air for

combustion if the structure does not provide enough air by

infiltration.  If the furnace is located in a building of tight

construction with weather stripping and caulking around the

windows and doors, follow the procedures in the air from

outside section.

Confined Space

A confined space is an area with a volume less than 50

cubic feet (1.42 m

3

) per 1,000 Btu (.29 kW) per hour of the

combined input rating of all appliances installed in that space.

This definition includes furnace closets or small equipment

rooms.

When the furnace is installed so that supply ducts carry air

circulated by the furnace to areas outside the space

containing the furnace, the return air must be handled by

ducts which are sealed to the furnace casing and which

terminate outside the space containing the furnace.  This is

especially important when the furnace is mounted on a

platform in a confined space such as a closet or small

equipment room.  Even a small leak around the base of the

unit at the platform or at the return air duct connection can

cause a potentially dangerous negative pressure condition.

Air for combustion and ventilation can be brought into the
confined space either from inside the building or from outside.

Air from Inside

If the confined space that houses the furnace adjoins a

space categorized as unconfined, air can be brought in by

providing two permanent openings between the two spaces.

Each opening must have a minimum free area of 1 square

inch (645 mm

2

) per 1,000 Btu (.29 kW) per hour of total

input rating of all gas fired equipment in the confined space.

Each opening must be at least 100 square inches (64516

mm

2

).  One opening shall be within 12 inches (305 mm) of

the top of the enclosure and one opening within 12 inches

(305 mm) of the bottom.  See Figure 3.

Air from Outside

If air from outside is brought in for combustion and ventilation,

the confined space must have two permanent openings.  One

opening shall be within 12 inches (305 mm) of the top of the

enclosure and one opening within 12 inches (305 mm) of

the bottom.  These openings must communicate directly or

by ducts with the outdoors or spaces (crawl or attic) that

freely communicate with the outdoors or indirectly through

vertical ducts.  Each opening shall have a minimum free

area of 1 square inch (645 mm

2

) per 4,000 Btu (1.17 kW)

per hour of total input rating of all equipment in the enclosure.

See Figures 4 and 5.  When communicating with the

outdoors through horizontal ducts, each opening shall have

a minimum free area of 1 square inch (645 mm

2

) per 2,000

Btu (.56 kW) per total input rating of all equipment in the

enclosure.  See Figure 6.

Figure 3

Equipment in Confined Space - All Air From Inside

NOTE: 

 Each opening shall have a free area of at least one square

inch per 1,000 Btu (645 mm² per .29 kW) per hour of the total input

rating of all equipment in the enclosure, but not less than 100 square

inches (64546 mm²).

Summary of Contents for GUH80C

Page 1: ...1 P506842 01 TABLE OF CONTENTS Unit Dimensions 2 GUH80C Parts Arrangement 3 GUH80C Gas Furnace 4 Shipping and Packing List 4 Safety Information 4 Use of Furnace as a Construction Heater 5 General 6 Co...

Page 2: ...turn air 4 Return air from both sides 5 Bottom and one side return air 2 Flue outlet may be horizontal but furnace must be vented vertically 3 Optional external side return air filter kit cannot be us...

Page 3: ...506842 01 Page 3 of 42 Issue 1132 Expanded View Figure 1...

Page 4: ...a licensed professional installer or equivalent service agency or the gas supplier WARNING Certifications These units are CSA International certified to ANSI Z21 47 In the USA installation of gas furn...

Page 5: ...must control the furnace The use of fixed jumpers that will provide continuous heating is not allowed The return air duct must be provided and sealed to the furnace Return air temperature range betwee...

Page 6: ...wndraft can occur in the furnace vent pipe or chimney As a result combustion gases enter the living space creating a potentially dangerous situation In the absence of local codes concerning air for co...

Page 7: ...aining the furnace the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace This is especially important when the fur...

Page 8: ...area of at least one square inch per 2 000 Btu 645 mm per 59 kW per hour of the total input rating of all equipment in the enclosure If the equipment room is located against an outside wall and the ai...

Page 9: ...washer have been removed the rigid leg will not touch the blower housing Setting Equipment WARNING Do not install the furnace on its front or its back Do not connect the return air ducts to the back...

Page 10: ...ty See Figure 9 2 Single side return air with optional return airbase See Figure 10 3 Bottom return air 4 Return air from both sides 5 Bottom and one side return air Figure 9 Single Side Return Air wi...

Page 11: ...ceiling joists When straps are used to suspend the unit in this way support must be provided for both the ends The straps must not interfere with the plenum or exhaust piping installation Cooling coi...

Page 12: ...wn the vent pipe and into the room This reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas This toxic gas might then be distributed throughout th...

Page 13: ...PFLOW POSITION Top Vent Discharge The unit will not vent properly with the flue transition pointed down in the 6 o clock position The combustion air inducer may be rotated clockwise or counterclockwis...

Page 14: ...brought into the unit from the bottom in order to accommodate the flue pipe Cut combustion air inducer tubing from 9 to 8 to avoid interference with inducer motor Remove make up box assembly 2 screws...

Page 15: ...es WARNING Use self drilling sheet metal screws or a mechanical fastener to firmly secure the vent pipe to the round collar of the flue transition If self drilling screws are used to attach the vent p...

Page 16: ...and free of obstructions Do not install a manual damper barometric draft regulator or flue restrictor between the furnace and the chimney Never connect a Category I appliance to a chimney that is serv...

Page 17: ...d means except vent connectors of listed type B vent material which shall be assembled according to the manufacturer s instructions Joints between sections of single wall connector piping shall be fas...

Page 18: ...onfigureations with zero lateral lengths are assumed to have no elbows in the vent system For all other vent configurations the vent system is assumed to have two 90 elbows For each additional 90 elbo...

Page 19: ...onfigureations with zero lateral lengths are assumed to have no elbows in the vent system For all other vent configurations the vent system is assumed to have two 90 elbows For each additional 90 elbo...

Page 20: ...Capacity Type B Double Wall Vents with Type B Double Wall Connectors Serving Two or More Category I Appliances Common Vent Capacity Type B Double Wall Vents with Type B Double Wall Connectors Serving...

Page 21: ...Two or more Category I Appliances Table 8 NOTE Single appliance venting configureations with zero lateral lengths are assumed to have no elbows in the vent system For all other vent configurations the...

Page 22: ...are located and other spaces of the building Turn on clothes dryers and any appliances not connected to the common venting system Turn on any exhaust fans such as range hoods and bathroom exhausts so...

Page 23: ...The piping must be supported at proper intervals every 8 to 10 feet 2 44 to 3 01 m with suitable hangers or straps Install a drip leg in vertical pipe runs to the unit 5 A 1 8 N P T plugged tap or pr...

Page 24: ...24 of 42 Issue 1132 Horizontal Applications Possible Gas Piping Configurations NOTE BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET Figure 27 NOTE BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABI...

Page 25: ...ice to protect the furnace s electronic controls Precautions will help to avoid control exposure to electrostatic discharge by putting the furnace the control and the technician at the same electrosta...

Page 26: ...neutral leg of the circuit being connected to one of the provided neutral terminals If a humidifier rated at greater than one amp is connected to this terminal it is necessary to use an external relay...

Page 27: ...506842 01 Page 27 of 42 Issue 1132 Wiring Diagram Figure 32 GUH80C 045A3M 070B3M 090B4M 090C5M 110C5M 135D5M...

Page 28: ...506842 01 Page 28 of 42 Issue 1132 Typical Field Wiring Diagram Figure 33 Figure 34 Integrated Control Automatic Hot Surface Ignition System...

Page 29: ...ns exactly a fire or explosion may result causing property damage personal injury or death WARNING 6 Move switch on gas valve to OFF Do not force See Figure 35 7 Wait five minutes to clear out any gas...

Page 30: ...curate reading shut off all other gas appliances connected to meter Supply Pressure Measurement A threaded plug on the inlet side of the gas valve provides access to the supply pressure tap Remove the...

Page 31: ...n air inducer operation before allowing ignition trial The switch is factory set and requires no adjustment Temperature Rise After the furnace has been started and supply and return air temperatures h...

Page 32: ...erature rise Fan Control The fan on time of 45 seconds is not adjustable The heat fan off delay amount of time that the blower operates after the heat demand has been satisfied may be adjusted by chan...

Page 33: ...140 445 145 Medium 735 125 140 180 200 160 GUH80C090B4M PERFORMANCE Less Filter External Static Pressure in w c Air Volume Watts at Various Blower Speeds High Medium High Medium Low cfm Watts cfm Watt...

Page 34: ...05 1340 175 2260 655 1945 425 1550 240 1400 185 0 20 2135 680 1865 465 1630 330 1280 190 2210 680 1895 450 1510 255 1350 200 0 30 2090 695 1830 480 1595 345 1235 200 2165 700 1850 465 1455 275 1285 21...

Page 35: ...all wiring for loose connections 2 Check for the correct voltage at the furnace furnace operating Correct voltage is 120VAC 10 3 Check amp draw on the blower motor with inner blower panel in place Uni...

Page 36: ...ve the combustion air inducer to avoid damaging blower gasket If gasket is damaged it must be replaced to prevent leakage 5 Remove the collector box located behind the combustion air inducer Be carefu...

Page 37: ...inserts 16 Reinstall collector box and combustion air assembly Reinstall all screws to the collector box and combustion air inducer Failure to replace all screws may cause leaks Inspect gaskets for a...

Page 38: ...seal between the return air and the room where the furnace is installed Return air duct Must be properly attached and provide an air seal to the unit Operating performance Unit must be observed during...

Page 39: ...epair parts are available through independent Allied Air dealers When ordering parts include the complete furnace model number listed on the CSA International nameplate Example GUH80C045A3M All servic...

Page 40: ...506842 01 Page 40 of 42 Issue 1132 START UP PERFORMANCE CHECK LIST UNIT SET UP...

Page 41: ...506842 01 Page 41 of 42 Issue 1132 UNIT OPERATION...

Page 42: ...mum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less t...

Reviews: