background image

507712-01

Page 6  of  36

Issue 1642

General

These instructions are intended as a general guide and do 

not supersede local codes in any way. Consult authorities 

having jurisdiction before installation.

In addition to the requirements outlined previously, the 

following general recommendations must be considered 

when installing one of these furnaces:

•  Place the furnace as close to the center of the air 

distribution system as possible. The furnace should 

also be located close to the chimney or vent termination 

point.

•  Do not install the furnace where drafts might blow 

directly into it. This could cause improper combustion. 

•  Do not block the furnace combustion air openings with 

clothing,  boxes,  doors,  etc. Air  is  needed  for  proper 

combustion and safe unit operation.

•  When the furnace is installed in an attic or other 

insulated space, keep insulation away from the 

furnace. 

NOTE

: The Commonwealth of Massachusetts stipulates 

these additional requirements:

•  Gas furnaces shall be installed by a licensed plumber 

or fitter only.

•  The gas cock must be “T handle” type.
•  When a furnace is installed in an attic, the passageway 

to and service area surrounding the equipment shall 

be floored.

Product Contains Fiberglass Wool.

Disturbing the insulation in this product during 

installation, maintenance, or repair will expose you to 

fiberglass wool. Breathing this may cause lung cancer. 

(Fiberglass wool is known to the State of California to 

cause cancer.)
Fiberglass wool may also cause respiratory, skin, and 

eye irritation.

To  reduce  exposure  to  this  substance  or  for  further 

information, consult material safety data sheets 

available from address shown below, or contact your 

supervisor. 

Comfort-Aire / Century

1900 Wellworth Ave.

Jackson, MI 49203

   WARNING

Combustion, Dilution & Ventilation Air

In the past, there was no problem in bringing in sufficient 

outdoor air for combustion. Infiltration provided all the air 

that was needed. In today’s homes, tight construction 

practices make it necessary to bring in air from outside 

for  combustion.  Take  into  account  that  exhaust  fans, 

appliance vents, chimneys, and fireplaces force additional 

air that could be used for combustion out of the house. 

Unless outside air is brought into the house for combustion, 

negative pressure (outside pressure is greater than inside 

pressure) will build to the point that a downdraft can occur 

in the furnace vent pipe or chimney. As a result, combustion 

gases enter the living space creating a potentially 

dangerous situation.

In the absence of local codes concerning air for combustion 

and ventilation, use the guidelines and procedures in this 

section to install this furnaces to ensure efficient and safe 

operation. You must consider combustion air needs and 

requirements for exhaust vents and gas piping.

A portion of this information has been reprinted 

with permission from the National Fuel Gas Code 

(ANSI-Z223.1). This reprinted material is not the complete 

and official position of the ANSI on the referenced subject, 

which is represented only by the standard in its entirety.

Insufficient  combustion  air  can  cause  headaches, 

nausea,  dizziness  or  asphyxiation.  It  will  also  cause 

excess water in the heat exchanger resulting in rusting 

and  premature  heat  exchanger  failure.  Excessive 

exposure  to  contaminated  combustion  air  will  result 

in safety and performance related problems. Avoid 

exposure to the following substances in the combustion 

air supply:
•  Permanent wave solutions
• 

Chlorinated waxes and cleaners

•  Chlorine base swimming pool chemicals
•  Water softening chemicals
•  De-icing salts or chemicals
•  Carbon tetrachloride
•  Halogen type refrigerants
•  Cleaning solvents (such as perchloroethylene)
•  Printing inks, paint removers, varnishes, etc.
•  Hydrochloric acid
•  Antistatic fabric softeners for clothes dryers
•  Masonry acid washing materials

   WARNING

Summary of Contents for GDD80A

Page 1: ...ON INSTRUCTIONS GDD80A Warm Air Gas Furnace Downflow Air Discharge This is a safety alert symbol and should never be ignored When you see this symbol on labels or in manuals be alert to the potential...

Page 2: ...ng Unit Dimensions Model Number A B C D GDD80A in mm in mm in mm in mm 045 3 14 1 2 368 13 3 8 340 13 330 4 3 4 121 070 2 070 3 090 3 17 1 2 446 16 3 8 416 16 406 6 1 4 159 090 4 110 4 21 533 19 7 8 5...

Page 3: ...sue 1642 Figure 1 BLOWER ASSEMBLY CABINET CONTROL BOX INTERNAL FLUE PIPE ASSEMBLY FLUE CHASE HEAT EXCHANGER GAS VALVE ACCESS PANEL BURNER BOX ASSEMBLY COMBUSTION AIR INDUCER ROLLOUT LOCATED INSIDE BUR...

Page 4: ...ng to the current National Fuel Gas Code ANSI Z223 1 The National Fuel Gas Code is available from the following address American National Standards Institute Inc 11 West 42nd Street New York NY 10036...

Page 5: ...bile homes recreational vehicles or outdoors Use of Furnace as a Construction Heater These units are not recommended for construction heating during any phase of construction Very low return air tempe...

Page 6: ...lem in bringing in sufficient outdoor air for combustion Infiltration provided all the air that was needed In today s homes tight construction practices make it necessary to bring in air from outside...

Page 7: ...taining the furnace the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace This is especially important when the fu...

Page 8: ...gs shall each have a free area of at least one square inch per 4 000 Btu 645 mm per 1 17 kW per hour of the total input rating of all equipment in the enclosure Inlet Air from Crawlspace Outlet Air to...

Page 9: ...met used with a flexible mounting leg The bolt and washer must be removed before the furnace is placed into operation After the bolt and washer have been removed the rigid leg will not touch the blowe...

Page 10: ...nsate trap and vent pipe installation The furnace may be installed on a combustible wood floor if an optional additive base is installed between the furnace and the combustible floor Installation on N...

Page 11: ...binet See Figure 13 NOTE Downflow combustible flooring kit is not used 1 Refer to reverse flow coil installation instructions for correctly sized opening in floor and installation of cabinet 2 When co...

Page 12: ...se flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas This toxic gas might then be distributed throughout the house by the furnace duct system Venting A...

Page 13: ...red to be an exterior chimney An exterior masonry chimney that is not tile lined must be lined with B 1 vent or a listed insulated flexible metal vent An exterior tile lined chimney that is sealed and...

Page 14: ...provided venting tables 3 The minimum vent capacity determined by the sizing tables must be less than the low fire input rating and the maximum vent capacity must be greater than the high fire input...

Page 15: ...st be resized Removal of the Furnace from Common Vent In the event that an existing furnace is removed from a venting system commonly run with separate gas appliances the venting system is likely to b...

Page 16: ...15 136 20 226 22 339 5 22 65 30 130 39 219 49 330 10 29 59 40 121 51 206 64 315 15 35 53 48 112 61 195 75 301 20 0 0 97 0 202 0 349 0 540 2 10 75 14 149 18 250 20 377 5 21 71 29 143 38 242 47 367 10 2...

Page 17: ...69 57 136 80 225 115 337 5 51 63 75 128 102 216 144 326 10 NR NR 95 116 128 201 182 308 15 NR NR NR NR 158 186 220 290 20 0 35 96 54 200 78 346 114 537 2 37 74 56 148 78 248 113 375 5 50 68 73 140 10...

Page 18: ...2 52 146 69 220 15 1 21 50 33 89 47 142 64 220 2 22 53 35 96 49 153 66 235 3 24 55 36 102 51 163 68 248 20 1 21 54 33 99 46 157 62 246 2 22 57 34 105 48 167 64 259 3 23 60 35 110 50 176 66 271 30 1 20...

Page 19: ...60 77 110 112 175 169 278 2 51 62 81 115 117 185 177 290 3 54 64 85 119 122 193 185 300 NOTE Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent...

Page 20: ...quire the installation of a manual main shut off valve and union furnished by the installer external to the unit The union must be of the ground joint type Compounds used on threaded joints of gas pip...

Page 21: ...8 07 260 7 36 240 6 80 220 6 23 205 5 80 195 5 52 1 1 4 31 75 1 380 35 052 1400 39 64 950 26 90 770 21 80 660 18 69 580 16 42 530 15 01 490 13 87 460 13 03 430 12 18 400 11 33 1 1 2 38 1 1 610 40 894...

Page 22: ...matic wiring diagram and troubleshooting and Figure 25 for field wiring The power supply wiring must meet Class I restrictions Protected by either a fuse or circuit breaker select circuit protection a...

Page 23: ...lay Generator Use Voltage Requirements The following requirements must be kept in mind when specifying a generator for use with this equipment The furnace requires 120 volts 10 Range 108 volts to 132...

Page 24: ...507712 01 Page 24 of 36 Issue 1642 Figure 24 Wiring Diagrams...

Page 25: ...LOWER MOTOR B3 OUTDOOR UNIT C R G Y W Y G R C W Y C R ON OFF B6 3 5 BURNERS IGNITOR FLAME SENSOR S47 FLAME ROLLOUT SWITCH S47 FLAME ROLLOUT SWITCH R33 J159 P159 3 Field supplied ACC Wire 5 S145 is use...

Page 26: ...RALS RED GREEN W C R Y G C 2 3 4 1 1 2 3 4 5 6 7 8 9 10 11 12 3 AMP 32 VAC FUSE Terminal Designations HUM Humidifier 120 VAC LINE Input 120 VAC XFMR Transformer 120 VAC EAC Electronic Air Cleaner 120...

Page 27: ...sing property damage personal injury or death WARNING Gas Valve Operation See Figure 27 1 STOP Read the safety information at the beginning of this section 2 Set the thermostat to the lowest setting 3...

Page 28: ...f flame is not detected after first ignition trial the ignition control will repeat steps 3 and 4 four more times before locking out the gas valve The ignition control will then automatically repeat s...

Page 29: ...set and require no adjustment Flame Rollout Switches This manually reset switches are located on the front of the burner box Pressure Switch The pressure switch is located in the heating compartment a...

Page 30: ...Nat 4 5 10 0 No Change 0 0625 3 5 No Change 0 0625 3 5 No Change 0 0625 3 3 51W01 0 0550 3 5 LP Propane 11 0 13 0 11K50 0 034 10 0 11K50 0 034 10 0 11K50 0 034 10 0 11K45 0 032 10 0 090 Nat 4 5 10 0 N...

Page 31: ...ill break and remake thermostat demand to the furnace and automatically reset the integrated control to begin the ignition sequence Service ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow...

Page 32: ...r manifold assembly to the vestibule panel and remove the assembly from the unit 7 Remove screws securing burner box and remove burner box 8 NOx units only Remove screw securing NOx insert Remove NOx...

Page 33: ...other sources of ignition to check for gas leaks CAUTION 24 If a leak is detected shut gas and electricity off and repair leak 25 Repeat steps 24 and 26 until no leaks are detected 26 Replace access p...

Page 34: ...ofessional installer or equivalent service agency or gas supplier Cabinet Parts Upper access panel Blower panel Top cap Control Panel Parts Transformer Integrated control Door interlock switch Circuit...

Page 35: ...507712 01 Page 35 of 36 Issue 1642 UNIT SET UP Start Up Performance Check List...

Page 36: ...507712 01 Page 36 of 36 Issue 1642 UNIT OPERATION...

Reviews: