Table 15.
Burner Orifice Conversion Kits at Varying Altitudes
Capacity
0 - 7,500 ft
(0 - 2,286 m)
7,501 - 10,000 ft
(2,286 - 3048m)
Natural to LP/
Propane
LP/Propane to
Natural
High Altitude
Natural Burner
Orifice Kit
High Altitude LP/
Propane Burner
Orifice Kit
All
11K50†
73W80*
51W01
11K45†
* Conversion requires installation of a gas valve regulator spring, which is provided with the gas
conversion kit.
† LP kits include low line pressure switch.
Pressure Switch Requirements at Varying Altitudes
Capacity
0 - 4500 ft
(0 - 1,373m)
4501 - 7500 ft
(1371 - 2286m)
7501 - 10000 ft
(2286 - 3048m)
045
No Change
No Change
11J09
070
No Change
11J12
10U93
090
No Change
11U70
10U93
110
No Change
11J12
10U93
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure
switch from 0-4500 feet (0-1370 m).
Summary of Contents for Century GDD95C Series
Page 30: ...507735 03 Page 30 of 53 Issue 1933 Figure 50 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC ...
Page 36: ...507735 03 Page 36 of 53 Issue 1933 045B3 070B4 090C4 110C5 Figure 57 Typical Wiring Diagram ...
Page 48: ...507735 03 Page 48 of 53 Issue 1933 Troubleshooting Heating Sequence of Operation ...
Page 49: ...507735 03 Page 49 of 53 Issue 1933 Troubleshooting Heating Sequence of Operation continued ...
Page 50: ...507735 03 Page 50 of 53 Issue 1933 Troubleshooting Cooling Sequence of Operation ...
Page 51: ...507735 03 Page 51 of 53 Issue 1933 Troubleshooting Continuous Fan Sequence of Operation ...