background image

 

 

 

 

 

 

 

COMET AG 

Herrengasse 10, CH-3175 Flamatt 

Tel. +41 31 744 9000, www.comet-xray.com 

XRCA-5001-OA, Doc.-No. 50005555 

Page 10 of 15 

 

 

 

 

 

 

  

Temperature maximum T3 

 

Press keys    (UP) and   (DOWN) simultaneously for 
4 seconds, P1 is shown on display 

Press SET-key and keep it pressed (value of P1 is 
shown on display) 

 

Note:

Hysterese of T3 adjusted at ± 2,5°C symmet-

 

rical to parameter P1.

 

 

Example: 

 

Value P1:

32.5°C 

 

 

 

Temperature maximum  

T3: 

 

fault indication ON: 

35.0°C 

 

fault indication OFF: 

20.0°C 

 

 

Adjust new value with keys  (UP) or   (DOWN) 

 

Release SET-key (P1 is shown on display) 

 

 

Press keys   (UP) and   (DOWN) simultaneously for 4  

 

seconds to return to run-mode (if there is no changing of  

 

parameters, the temperature controller returns automatically  

 

into run-mode after 45 seconds). 

 

Printed from SAP on 7.09.2015

SAP-DocNr: 50005555_001

Summary of Contents for XRCA-5001-OA

Page 1: ...engasse 10 CH 3175 Flamatt Tel 41 31 744 9000 www comet xray com XRCA 5001 OA Doc No 50005555 Page 1 of 15 Industrial X Ray Chiller Manual XRCA 5001 OA For OEM Printed from SAP on 7 09 2015 SAP DocNr...

Page 2: ...y Version Date Author Amendment s Status 1 0 03 31 2010 M Schmid Layout Structure 07 23 2010 St Haferl Released 2 0 10 30 2012 R Moser Layout Structure 3 0 07 01 2013 R Moser Update Chapter 2 3 4 0 30...

Page 3: ...Run cooling unit always with correct coolant level otherwise damage of pump may occur Only use cooling hoses with sufficient pressure and coolant resistance Never operate damaged or leaking equipment...

Page 4: ...5 Page 4 of 15 Contents 1 Description 5 2 Technical data 6 3 Performance chart 7 4 Setting to work 8 5 Settings 9 6 Maintenance 11 7 Outline drawing 12 8 Circuit Diagrams 13 8 1 Electrical diagram 13...

Page 5: ...um cooling capacity of the cooling unit depends on the ambient and the fluid temperature The cooling capacity is 5000W related to 40 C ambient temperature and 30 C 2 C fluid temperature Cooling hoses...

Page 6: ...30 V available in 50 Hz or 60 Hz version Current consumption 8 2 A Noise level 70 dB A distance 1 m in any direction Airflow at 50Hz 60Hz 3400 m3 h 4400 m3 h Safety class IP 33 Environmental specifica...

Page 7: ...COMET AG Herrengasse 10 CH 3175 Flamatt Tel 41 31 744 9000 www comet xray com XRCA 5001 OA Doc No 50005555 Page 7 of 15 3 Performance chart Printed from SAP on 7 09 2015 SAP DocNr 50005555_001...

Page 8: ...rake at caster remove side cover connect hoses with cooling unit remove plug of filler fill the cooling unit with oil up to top indicator establish electrical connection Note Operate equipment only wi...

Page 9: ...LED on cooling unit ready LED off Temperature below anti freezing running of refrigeration system impossible Oil outlet temperature rated value T1 Press SET key and keep it pressed rated value is sho...

Page 10: ...Hysterese of T3 adjusted at 2 5 C symmet rical to parameter P1 Example Value P1 32 5 C Temperature maximum T3 fault indication ON 35 0 C fault indication OFF 20 0 C Adjust new value with keys UP or D...

Page 11: ...er of the cooling unit clean Regularly once a week check this heat exchanger and if necessary clean it Clean fins of heat exchanger Remove dust by forcing it out in the opposite direction from which i...

Page 12: ...COMET AG Herrengasse 10 CH 3175 Flamatt Tel 41 31 744 9000 www comet xray com XRCA 5001 OA Doc No 50005555 Page 12 of 15 7 Outline drawing Printed from SAP on 7 09 2015 SAP DocNr 50005555_001...

Page 13: ...Herrengasse 10 CH 3175 Flamatt Tel 41 31 744 9000 www comet xray com XRCA 5001 OA Doc No 50005555 Page 13 of 15 8 Circuit Diagrams 8 1 Electrical diagram Printed from SAP on 7 09 2015 SAP DocNr 50005...

Page 14: ...COMET AG Herrengasse 10 CH 3175 Flamatt Tel 41 31 744 9000 www comet xray com XRCA 5001 OA Doc No 50005555 Page 14 of 15 8 2 Block diagram Printed from SAP on 7 09 2015 SAP DocNr 50005555_001...

Page 15: ...OMET AG Herrengasse 10 CH 3175 Flamatt Tel 41 31 744 9000 www comet xray com XRCA 5001 OA Doc No 50005555 Page 15 of 15 9 Declaration of conformity Printed from SAP on 7 09 2015 SAP DocNr 50005555_001...

Reviews: