Comet T8148 Instruction Manual Download Page 5

IE-SNC-T81(2)xx-01 

 

  5 

 

Typical application wiring 

.

 

Outputs 4-20 galvanically isolated

 

 

 

       

Outputs 4-20mA galvanically non-isolated 

 
 
 
 
 
 
 
 
 
 
 

 

 

Outputs 0-10V 

                                 

 

  

Range of supply voltages and resistor values

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

       Uss . . . . . 9 to 30Vdc 

 

 

 

 

 

 

 

       Uss1 . . . . 9 to 30Vdc  

 

 

 

 

 

 

 

 

 

 

       Uss2 . . . . 9 to 30Vdc 

 

 

 

 

 

 

 

       R1max[Ω] = 50 * Uss1[V] - 450 

 

 

 

 

 

 

 

       R2max[Ω] = 50 * Uss2[V] - 450 

 

 

 

 

 

 

 

       Rmax[Ω] = 50 * Uss[V] - 450 

 

 

 

 

 

 

 

       Rzmin . .  20 kΩ 

 

 

 

 

 

 

 

 
 

 

 

LCD Info mode 

The output range settings can be verified without a use of the computer by 

pressing  the  button  on  the  left  side  of  the  device    (button  is  placed  behind 
small hole - see picture). For button pressing use thin instrument, for example 
paper clip. 

 

 
 

 
Upper line of the LCD display shows value of CO2 
concentration  corresponding  to  output  current  4mA 
(output voltage 0V). 

 

 
 

Press  the  button  again  and  upper  line  of  the  LCD 
display  shows  value  of  CO2  concentration 
corresponding  to  output  current  20mA  (output 
voltage 10V). 
 

 

 

T8148 

 

T8248 

 

 

 

T8148 

 

T8248 

 

 

 

Summary of Contents for T8148

Page 1: ...48 Programmable indoor transmitter of temperature and CO2 concentration with 4 20mA output T8248 Programmable indoor transmitter of temperature and CO2 concentration with 0 10V output Instruction Manu...

Page 2: ...rary in FAST mode no software filter is used for calculating the output value This fact adds a noise of typ 30ppm which has to be considered in terms of accuracy Of principle measurement is the measur...

Page 3: ...s heating elements and other heat sources air handlers windows doors into racks and shelves and similar places For buildings with less thermal insulation there is not suitable to place them on externa...

Page 4: ...t screwdriver beyond the fastening member about 2 cm deep Then slightly move screwdriver in arrow direction it unlock fastening member and the device is partially opened Remove the screwdriver and tak...

Page 5: ...utput range settings can be verified without a use of the computer by pressing the button on the left side of the device button is placed behind small hole see picture For button pressing use thin ins...

Page 6: ...ation cable to the PC Installed USB driver detect connected cable and create virtual COM port inside the PC Unscrew four screws of the device lid a remove the lid If device is already installed to mea...

Page 7: ...se when the device is connected to the PC via the optional SP003 communication cable and external power supply is not used Technical parameters T8148 temperature and CO2 concentration transmitter Outp...

Page 8: ...C Operating humidity range 5 to 95 RH no condensation Operating pressure range 850 to 1100 hPa Recommended interval of calibration 5 year CO2 2 years temperature Protection IP20 EMC EN 61326 1 EN 5501...

Reviews: