Comet T3319 Instruction Manual Download Page 3

IE-SNC-T33(4)19+T73(4)11-09 

 

communication protocol: 

Modbus RTU

 

device address: 

01

 

communication speed: 

9600Bd, without parity, 2 stop bits

 

display:  

switched ON 

value displayed at higher line: 

temperature (temperature / pressure) 

– by device type

 

value displayed at lower line: 

relative humidity only 

temperature unit:

 

°C 

pressure unit:

 

hPa 

preset computed value: 

dew point temperature 

correction for altitude: 

0 hPa 

(absolute pressure)

 

 

Device installation 

Device is designed for wall mounting. There are two mounting holes at the sides of the case. It 

is NOT recommended to use the device for long time under condensation conditions. It could be the 
cause  of  water  steam  condensation  inside  the  sensor’s  cover  into  water  phase.  This  liquid  phase 
stays  inside  sensor’s  cover  and  can’t  escape  from  the  cover  easily.  It  can  dramatically  increase 
response time to relative humidity change. If water condensation occurs for longer time it can cause 
sensor damage. Similar effect can occur under water aerosol conditions. Don’t connect device while 
power  supply  voltage  is  on.  Interconnection  terminals  for  T3319(P),  T3419(P),  T7311  and  T7411 
devices are accessible after unscrewing four screws and removing  the lid. Measuring temperature, 
relative  humidity  and  eventually  pressure  sensors  are  non-removable  device  parts.  Lace  the  cable 
through a gland at the case wall. Connect the cable to terminals with respecting the signal polarity 
(see  figure).  Terminals  are  self-clamping  and  can  be  opened  by  a  suitable  screwdriver.  For  the 
opening, insert the screwdriver to smaller terminal hole and lever by him. Do not forget to tighten 
glands and case lid with inserted packing after cables connecting. It is necessary for  warranting of 
protection  IP65.  Connect  complementary  female  connector  for  T3319L,  T3419L,  T7311L  and 
T7411L transmitters in accordance with the table in Appendix B of this manual.  

Devices  T3319(P)  and  T7311  are  supplied  with connection  cable  equipped  with  connector 

for  connection  to  RS232  interface.  For  devices  with  RS485  output  there  is  recommended  to  use 
shielded twisted copper cable, maximal length 1200m. The cable must be located at indoor rooms. 
Nominal  cable  impedance  should  be  100 Ω,  loop  resistance  max.  240 Ω,  cable  capacity  max. 
65 pF/m. Outside diameter of the cable for T3419(P) and T7411 connection must be from 3 to 6.5 
mm. Suitable cable is  e.g. SYKFY 2x2x0.5 mm

2

, where one wire pair serves for device powering 

and the other pair for communication link. For devices T3319L, T3419L, T7311L and T7411L use 
cable with respect to female connector parameters. Do NOT connect shielding at connector side. 

The cable should be led in one line, i.e. NOT to „tree“ or „star“. Termination resistor should 

be  located  at  the  end.  For  short  distance  other  topology  is  allowed.  Terminate  the  network  by  a 
termination  resistor.  The  value  of  the  resistor  is  recommended  about  120 

.  For  short  distance 

termination resistor can be left out. 

The cable should not be led in parallel along power cabling. Safety distance is up to 0.5 m, 

otherwise undesirable induction of interference signals can appear. 

Electrical  system  (wiring)  may  do  only  worker  with  required  qualification  by  rules  in 

operation. 

The devices T3319P and T3419P are designed to measure pressured air. It is good to mount 

probe  directly  into  high  pressure  area  (i.e.  air  pressured  pipe)  if  it  is  possible.  There  is  other 
possibility to use flow chamber SH-PP, see Appendix C. 

 
 

Before you remove probe of the transmitter T

xxxx

P, make sure that the pressure in a 

pressure chamber (duct, pipe …) and the ambient pressure are in equilibrium 

 

Summary of Contents for T3319

Page 1: ...y and other derived humidity values T3319 T3319P T3419 T3419P Programmable transmitter of atmospheric pressure temperature relative humidity and other derived humidity values T7311 T7411 with RS232 RS...

Page 2: ...ter Temperature relative humidity eventually pressure sensors are non removable device parts excepting T3319P and T3419P transmitters pressure sensor is placed inside the electronic case Measured and...

Page 3: ...ecessary for warranting of protection IP65 Connect complementary female connector for T3319L T3419L T7311L and T7411L transmitters in accordance with the table in Appendix B of this manual Devices T33...

Page 4: ...11 09 4 Dimensions T3319 P T7311 transmitter with RS232 serial output probe for compressed air measurement Typical application wiring of T3319 P and T7311 power from communication port power from ext...

Page 5: ...IE SNC T33 4 19 T73 4 11 09 5 Dimensions T3419 P T7411 transmitter with RS485 serial output probe for compressed air measurement Typical application wiring of T3419 P T7411 connection of terminals...

Page 6: ...ce cover and shortly press button next to connection terminals jumper should be opened Actual adjusted address of the device is displayed on LCD display at decimal base for HWg Poseidon s communicatio...

Page 7: ...t bit data word in format 1 start bit data word 8 bit LSB first 2 stop bits1 without parity Device supports communication speed from 110Bd to 115200Bd Sent request and response have syntax ADDRESS OF...

Page 8: ...ariable Unit Address hex X Address dec X Format Size Status Dew point temperature C F 0x0035 53 Int 10 BIN16 R Absolute humidity g m3 0x0036 54 Int 10 BIN16 R Specific humidity g kg 0x0037 55 Int 10 B...

Page 9: ...on protocol device address sets to 01h and communication speed to 9600Bd after button press there is dEF message blinking at LCD display Six seconds later message dEF stays shown it means manufacturer...

Page 10: ...re is 999 9 hPa correct value This state appears in case of Measured temperature is higher than approximately 600 C i e high non measurable resistance of temperature sensor probably opened circuit Rel...

Page 11: ...or state of value g kg reading next to this symbol is calculated specific humidity or mixing ratio depends on device setting or error state of value If specific enthalpy is selected there is shown onl...

Page 12: ...limited in accordance with the graph below The value computed from air temperature and relative humidity Dew point temperature Range 60 to 80 C 76 to 176 F Accuracy 1 5 C 2 7 F at ambient temperature...

Page 13: ...mesh sensor cover F5200B and bronze sensor cover F0000 selectable option air flow approximately 1 m s temperature T3319 L T3419 L T7311 L T7411 L t90 6 min temperature step 20 C 36 F T3319P T3419P t9...

Page 14: ...ic compatibility complies EN 61326 1 Not allowed manipulation It is not allowed to operate the device under conditions other than specified in technical parameters Devices are not designed for locatio...

Page 15: ...ese internal resistors can be connected to the bus by connecting the corresponding pins of CANON connector for more information see the operation manual for ELO E214 The ELO E06D converter is an optio...

Page 16: ...interrupting the main line closing valve 5 the sample flow is regulated by this valve Measurement accuracy is typically not affected by the sample flow rate but at low speeds increasing response time...

Reviews: