IST-47RTS282EO
Istruzione / User’s Manual / Manuel d’utilisation
Pag.6/11
Comelit Group S.p.A
. - Via Don Arrigoni 5 - 24020 Rovetta S. Lorenzo BG Italy
Tel. +39 0346 750 011 - Fax +39 0346 71436
Sensor operating limits:
the electro-chemical cell, in any case, should not be exposed to temperatures lower
than -40° or higher than 60°C. The electrochemical cell should not be exposed to an over-range concentration of
30 % O
2
. If this condition occurs, we suggest replacing the sensor.
Safety:
Oxygen sensors contain a small quantity potassium acetate solution which is corrosive. Normally this mate-
rial would only leak out as a result of either mechanical damage or an incorrect instrument use beyond the limits of
its operational functioning. These sensors also contain small amounts of lead, lead oxide, platinum, silver, carbon
and antimony. If the user comes into contact with the oxygen sensor contents the affected area should be washed
with a copious supply of water.
Cross sensitivity to other gases:
The electrochemical cell employed has a good resistance towards products
such as sprays, detergents, ammonia, glues and paints.
However, in case of products containing substances in
great quantity, these could interfere with the Sensor and cause false alarms.
We recommend ventilating the room
when products like these are used. Volatile organic solvents in great quantity cause false alarms, and then the cell
needs one or more hours in clean air to recover the normal sensitivity conditions.
TEST and CALIBRATION
PAY ATTENTION
:
This procedure has to be made with extreme attention and by authorized and trained
people; because starting this procedure it will start both Outputs (relays) causing the activation of con-
nected alarm devices.
Operation Check, Calibration in Air and Fine mA ADJ Output:
are different code protected functions. To access
these functions is necessary to insert the relevant “
Code
" through the keys F1s and F2. To have the key pressure
recognized, hold pressing it for around a second (
until the Green Led doesn't switch off for a moment
). Then the next key
can be pressed. In case of error all it takes is waiting around 10 seconds and the sequence is automatically erased.
The
Calibration Check
is a function code free.
Calibration Kit, Sample Gas Bottles
(
for Calibration Check
) please, using a mixture:
about 16%v/v Oxygen (O
2
) in Nitrogen
It is possible to use either the disposable cylinders with adjust valve or the high pressure ones with reduction gear.
It is necessary to use
the calibration kit
model TC011
(
for non-corrosive gases
)
or TC014 (
Stainless steel
).
“INSTRUMENT OPERATION CHECK” (
Check Code
: F2, F2, F1, F1)
:
this function allows to effect a functional test
of the equipment. After having put the system in safety and inserted the "
Code Test
", all Led are switched off and all
the relays are disarmed. Then they will switch on in sequence, the Led, from the yellow up to the 3° red. To the
lighting of the various Led it corresponds the activation of the relevant relays (
relay "FAULT" with the yellow Led, relay
"ALARM1" with the 1° red Led, relay "ALARM2" with the 2° red Led, relay "ALARM3" with the 3° red Led
). At the end all the Led will
remain lighted for around 5 seconds, then the central returns at the conditions of normal operation. It is advisable to
perform this operation every 6-12 months according to the use.
Note: this function is not working if the 1° and/or the 2° and/or the 3° red Led have already turned on
“CALIBRATION IN AIR” (
Calibration Code
: F2, F2, F2, F1, F2, F1)
:
this function allows completely recalibrate the
sensor at 20.9%v/v in air. This procedure when it is launched will automatically until the end.
Warning
: to guarantee that no errors of elaboration happen, the rare possibility exists that during the Calibration
the
yellow LED switch off every 8 seconds,
in this case interrupt the procedure, switch off and witch on the instru-
ment and repeat the Calibration. If condition persists it will be necessary to send the detector to the supplier for the
reparation.
Important note:
During Calibration routine the mA output indicates 0mA
.
The Calibration can be done in clean air only (
environment without the presence of flammable or other polluting gas
). With the
keys perform the “
Calibration
Code
". Wait until the Yellow and Green Led switch on fix and the 1
st
red Led starts to
flash (the 3
th
Led Red
switch on to indicate the calibration working). Wait while the 1
st
red Led switched off. At this
point we can have two possibilities:
Yellow and Green Led illuminates:
the calibration routine has correctly been performed. The detector automatically
switches off in 8 seconds, and restart into normal operating mode. (
See chapter OPERATIONAL DESCRIPTION “Preheating”
).
Yellow LED illuminates:
the calibration routine has failed. The detector automatically switches off and restarts in
8 seconds and repeats the procedure without inserting again the sequence. If condition still persists after the re-
placement of the cartridge it will be necessary to send the detector back to the manufacturer for reparation.
Important
: If the environment is much polluted and there is doubt that the concentration of oxygen is 20.9%v/v,
you can use an air cylinder with
20.9%v/v of O
2
or use a gas balloon filled with fresh air. In this case, before exe-
cuting the "
Calibrating Code
" inserts the TC011 over the sensor holder, adjust the flow of air, so that the flow meter
indicates approximately 0.3 l / min (
see Fig.3
).
“CALIBRATION CHECK” (
no Code required
)
:
although the sensor operation is guaranteed if it is regularly per-
formed successfully "Calibrating in Air", it is possible to simulate the response of the detector using sample gas cyl-
inder with a mixture 16%v/v Oxygen in nitrogen. Insert the TC011 over the sensor holder; adjust the sample gas
cylinder valve as the flow meter indicates around 0.3 l/mins (
see Fig.3
), wait for 1÷2 minutes or until the instrument
activates Alarms as shown in chapter “
Operational Description
”.
If the result is different, is necessary to recalibrate the
sensor (
see “Calibration in Air”
).
Then, close the gas cylinder
and remove TC011,
wait 2÷3 minutes, until the instru-
ment restores the normal working conditions
.
NOTE
: further to the above, if the mA output is also used, verify with a voltmeter connected to the Test-Point
“
TESTmA
” (
see Fig.2
), the value reach a
174mV
value in normal clean air condition (20.9%v/v).