Table 1
Value
Unit
Notes
Pyh
,
Pyt
-
Pt100: -100…850 °C, Pt1000: -100…600 °C
Px1
,
Px2
-
PTC 1k: -50...150 °C, PTC 2k: -50...150 °C
R)1
-
resistive linear: 0…1 k
Ω
yxb
-
T/C "B": 200...999 °C
yxJ
-
T/C "J": -20...999 °C
yx"
-
T/C "K": -20...999 °C
yxr
-
T/C "R": 0...999 °C
yxS
-
T/C "S": 0...999 °C
yxt
-
T/C "T": -40...400 °C
u
-
voltage linear: 0…100 mV
I0
,
I4
-
current linear: 0…20 mA, 4…20 mA
w10
-
voltage linear: 0…10 V
.C
,
.F
-
°C, °F
0, 0.0, 0.00
-
when indicating values with the input-signal measurement unit (
ISU
)
-199 ... 999
ISU
These parameters make sense ONLY in case of a linear input signal.
-199 ... 999
ISU
display offset value
1…254 -
!2
,
@4
,
$8
,
(6
bps
1200, 2400, 4800 (factory-set), 9600 bps
0 … 999
ISU
used for input peak filtration; value '0' cancels the filtration
0 … 999
-
This parameter and the following one define a low-pass input filter.
0 …
M
ISU temperature: whole part of
M
≤
100; linear:
M
= 25% of input range
within input range
ISU
These parameters keep the set points in safe limits,
preserving them from random changes.
coo
,
hEA
-
'
coo
ling' - activates over set point, '
hea
ting' - activates under set point
0 ... 999
ISU
less than (high range limit -
Set Point 1
)
0 ... 999
ISU
less than (
Set Point 1
- low range limit)
0 ... 999
sec.
pulse duration; value '0' disables pulse mode
0 ... 999
sec.
pause duration; value '0' disables pulse mode
0 ... 999
sec.
Value '0' disables hold mode.
-199 ... 999
ISU
within range
SP Limit Low
...
SP Limit High