10
CONTROL PANEL INSTRUCTIONS
Set temperature
1.
Press
and the set temperature will flash on the display.
2.
Repeatedly press
/
to modify and store the displayed values.
3.
Press
to exit and the storage temperature is displayed.
NOTE: If no button is pressed within 10 seconds, the storage temperature will be displayed.
Refrigeration indicator light
During refrigeration, this indicator light will illuminate;
When the storage temperature is constant, this indicator light will go out;
During the delay start, this indicator light will flash.
Defrosting indicator light
During defrosting, this indicator light will illuminate;
During the delay start, this indicator light will flash.
Parameter setup
1.
Press and hold
for about 6 seconds to enter the parameter setup mode.
E1 will flash on the display.
2.
Repeatedly press
to select the parameter required.
Parameter
Function
Setting range
Default
E1
Lower setpoint limit
-50°C ~ Set temperature
-20°C
E2
Higher setpoint limit
Set temperature ~ +99°C
8°C
E3
Temperature hysteresis
1°C ~ 20°C
3°C
E4
Compressor start delay time
0 ~ 10 min.
0 min.
E5
Offset on room temperature
-10°C ~ 10°C
0°C
3.
Press
/
, the value of parameter will be displayed and can be modified and stored.
If no button is pressed within 10 seconds, it will return to normal operation mode.