13
TABLE for medium current values of 2,5 Amps
C/K
C = First bank power expressed in kvar (400V)
2,5
5
6
10
12,5
20
25
40
50
T.A.
K
30/5
6
0.3
0.5
0.5
-
-
-
-
-
-
50/5
10
0.3
0.3
0.4
0.5
-
-
-
-
60/5
12
0.3
0.3
0.4
0.5
0.5
-
-
-
-
80/5
16
0.2
0.3
0.3
0.5
0.5
0.5
-
-
-
100/5
20
0.2
0.3
0.3
0.3
0.4
0.5
0.5
-
-
150/5
30
0.2
0.2
0.3
0.3
0.3
0.5
0.5
0.5
-
200/5
40
0.2
0.2
0.2
0.3
0.3
0.3
0.4
0.5
0.5
250/5
50
0.1
0.2
0.2
0.3
0.3
0.3
0.3
0.5
0.5
300/5
60
0.1
0.2
0.2
0.2
0.3
0.3
0.3
0.4
0.5
400/5
80
0.1
0.2
0.2
0.2
0.2
0.3
0.3
0.3
0.4
500/5
100
0.1
0.1
0.2
0.2
0.2
0.3
0.3
0.3
0.3
600/5
120
0.1
0.1
0.1
0.2
0.2
0.2
0.3
0.3
0.3
800/5
160
0.1
0.1
0.1
0.2
0.2
0.2
0.2
0.3
0.3
1000/5
200
0.1
0.1
0.1
0.1
0.2
0.2
0.2
0.3
0.3
1200/5
240
0.1
0.1
0.1
0.1
0.1
0.2
0.2
0.2
0.3
1500/5
300
0.1
0.1
0.1
0.1
0.1
0.2
0.2
0.2
0.2
2000/5
400
0.1
0.1
0.1
0.1
0.1
0.1
0.2
0.2
0.2
2500/5
500
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.2
0.2
3000/5
600
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.2
0.2
4000/5
800
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.2
5000/5
1000
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
When the CT secondary current signal is lower than 2 amps, the C/K value should be increased by 0,1
•
When using the regulator on 220/230 Vac networks the C/K values should be doubled.
•
“-” means installation of C.T. with primary value too small.
••••
PF setting
After setting the C/K value, press the
Select
button again for 4 secs to indicate the selected PF required. At
the same the red led
PF
will illuminate. To release the
Select
button and use the
+
or
_
buttons to
change the selection. A PF of 0.95 is recommended.
Example:
setted C/K = "0.3"
setted PF = "0.97"
The regulator will switch bank to achieve a PF value within 0.94 and 1.00 (0.97 ± 0.03)
The “-” led near the two numbers display is illuminate if the P.F. value is more than 1.00.
6.1 SAVING the SET VALUES
By pressing the
Prog.
button the C/K and P.F. values which have been selected will be saved and the Regulator
works in AUTOMATIC condition.