Mains pro 1.6.1 Global Guide
23
LED
Color
Meaning
TRIP
Red
The unit has the appropriate outputs in TRIP position and the unit is
sensing a fault situation
Red
flashing
The unit has the appropriate outputs in TRIP position, but the unit is
sensing fault-free situation. Fault reset is possible.
Nothing
The unit has no output in TRIP position
U
Red
flashing
Voltage of any phase is above threshold for 1st or 2nd stage
overvoltage
Red
Voltage of any phase is under threshold for 1st or 2nd stage
undervoltage
Orange
flashing
Voltage unbalance (amplitude) is indicated.
If activated together with LED f and LOM, indicates incorrect phase
rotation
Orange
Negative sequence overvoltage or Positive sequence undervoltage
is indicated.
If activated together with LED f and LOM, indicates incorrect
polarity of one phase
Green
All voltages are in fault-free state
Green
flashing
Floating 10 minutes average overvoltage (page 34)
is detected
Nothing
Over/under voltage protections are not enabled by setpoint and no
other voltage failure is sensed
f
Red
flashing
Frequency as sensed on terminals Ua is above threshold for 1st or
2nd stage overfrequency
Red
Frequency as sensed on terminals Ua is under threshold for 1st or
2nd stage underfrequency
Orange
flashing
Together with LED U and LOM, indicates incorrect phase rotation
Orange
Together with LED U and LOM, indicates incorrect polarity of one
phase
Green
Frequency, rotation and phases polarity are in fault-free state
Nothing
Over/under frequency is protections are not enabled by setpoint and
no other indicated failure is sensed
LOM
Red
Vector shift or ROCOF protection was indicated and Fault reset
was not yet done
Orange
flashing
Together with LED U and f, indicates incorrect phase rotation
Orange
Together with LED U and f, indicates incorrect polarity of one phase
Nothing
None of Vector shift or ROCOF failure is detected or neither Vector
shift nor ROCOF protections are not enabled by setpoint and no
other indicated failure is sensed
Meaning of signaling LEDs