7 List of possible events
InteliVision 5 CAN screen texts
Description
Detecting
Controller detection sequence is in progress. Text disappears when controller
is detected.
Checking
Controller configuration sequence is checking. Text disappears when
controller is detected.
Reading cfg. Table
Controller configuration reading is in progress. Text disappears when
controller is detected.
Preparing
Display setting Ok.
Running
Indication of running display.
Wrong Display HW
SW and HW mismatch. Correct firmware has to be programmed.
Invalidate configuration table Error
Configuration table is invalid. Controller configuration has to be
reprogrammed or upgraded.
Unsupported controller Error
Controller is not supported.
Unsupported cfg. table format Error
Controller configuration table is not supported. InteliVision 5 firmware
upgrade is necessary.
Mismatch parameters length Error
Controller parameters mismatch. Controller configuration upgrade is
necessary.
Mismatch const values length Error
Controller constants mismatch. Controller configuration upgrade is necessary.
Mismatch values length Error
Controller values mismatch. Controller configuration upgrade is necessary.
Mismatch val states length Error
Controller values states mismatch. Controller configuration upgrade is
necessary.
Communication Error
Controller is detected; CAN communication level is not defined correctly.
Reason of this behavior could be: CAN bus line is not terminated properly,
environment disturbance is present or CAN line is too long.
Terminal addr collision Error
Another CAN bus connected equipment uses the same Terminal address for
a given controller. Change Terminal address is necessary.
Screen template missing Error
Unsupported controller firmware, missing InteliVision 5 support.
Screen template version Error
Unsupported controller screen. InteliVision 5 firmware has to be updated.
Font not valid Error
Corrupted display font. Font programming was not done properly. Display
firmware/font programming is necessary.
Font format not supported Error
Unsupported font, InteliVision 5 font or firmware is necessary.
Bitmaps not valid Error
Bitmaps (generator, engine, fuel and etc...) Firmware upgrade is necessary.
Bitmaps format not supported Error
Unsupported bitmaps format. (Engine, gen-set and etc...) Firmware upgrade is
necessary.
Default lang. not supported Error
Default/Defined language error/not supported. Language change or code
page change is necessary.