2.4 Power supply, analog input and binary output
connection
See
Installation and wiring (page 14)
chapter for pin-out and dimensions description.
Note:
Binary output is used for Horn function without possibility of configuration (pin 3, pin 4). It is Solid State
Relay with galvanic separation - like free contact. Max 36VDC / 0,5A.
Note:
Pin 2 – Analog / Binary Input for display and buttons backlit control. Connect resistive pot for continuous
backlit change: 0
W
~ 0%; 2400
W
~ 100%. Or just place contact to switch between 0% and 100% intensity.
Note:
The 1A standard diode in power feeding circuit is important to meet MARINE requirements given by