How to view Connection screen on IG-Display?
Press
↑
button when in Info screen to see information about IG-Display hardware version and
properties and actual state of communication with the master controller.
How to change the display backlight intensity?
Hold down the ENTER and then press ESC. On the display you can see Controller INFO screen for
10 seconds.
Press and hold ENTER when in INFO screen and use
↑
or
↓
to adjust the best display backlight.
Backlight intensity is set for one of the two modes, depending on the activity of configurable binary
input
Alt brightness
(IG-NT/EE and modifications). For IG-Display and IS-Display modules, this binary
input is located in the Power connector and it’s function is fixed (not configurable).
IS-Display with address 1 reads analog input
LCD brightness
on IS-NT-BB and changes accordingly
display backlight intensity in the range 0-100%.
Hint:
Backlight intensity change available from the MEASUREMENT screens only.
How to find active alarms?
Select Alarmlist menu item and press ENTER or press
←
in MEASUREMENT IO or MEASUREMENT
CU menu.
Inverted alarms are still active. Non-inverted alarms are not active, but not yet confirmed.
Press FAULT RESET to accept all alarms (an asterix mark disappears when an alarm is accepted by
FAULT RESET). Non-active alarms immediately disappear from the list.
Active alarm list appears on the screen automatically when a new alarm comes up and Main
MEASUREMENT screen was selected.
Hint:
Alarm list does not activate automatically if the display is switched to any other screen than the first
one of MEASUREMENT (typically the screen that shows menu selector on the upper). The automatic
jump to the alarm list screen will not occur if you are listing through the measured values, set points or
history!
If setpoint
Engine protect
:
ResetActAlarms
is set to DISABLED, only inactive alarms can be reset.
If an active alarm is present in the alarm list, controller display blinks every 30 seconds.
When to use GCB ON/OFF button?
The button is disabled in AUT mode.
In MAN and TEST modes it is enabled, but before closing of the circuit beaker, generator voltage and
frequency must be within limits. The controller has internal protection to avoid the breaker closure
without synchronizing.
The controller recognizes automatically:
•
if there is mains / bus voltage and the gen-set shall be synchronized before closing the GCB
•
or if there is no voltage on the bus and the GCB can be closed without synchronizing.
When to use MCB ON/OFF button?
The button is disabled in AUT mode.
Use this button in MAN or TEST mode to close or open the MCB.
Be careful while doing this,
because you can disconnect the load from the mains!!!