InteliNano-NT Plus, SW version 2.0.1.x,
©ComAp – July 2015
74
A05 Mains Overfrequency
Units:
percentage [%]
Step:
1 %
Range:
– 150 %
Default value:
102 %
Delay:
0,1 s
Threshold for detection of mains failure due to overfrequency. The setpoint is adjusted relative to the
system nominal frequency (setpoint
A06
Mains Underfrequency
Units:
percentage [%]
Step:
1 %
Range:
50
Default value:
98 %
Delay:
0,1 s
Threshold for detection of mains failure due to underfrequency. The setpoint is adjusted relative to the
system nominal frequency (setpoint