InteliMains 210 Global Guide
527
Related applications
MCB, MGCB, BTB
Description
This alarm evaluates the Bus Left voltage between phases L1 a L2. The following
setpoints are related to it:
Bus Left Undervoltage (page 188)
Bus Left < > Voltage Delay (page 189)
Note:
Alarm is active only in case the setpoint
is
set to 3Ph3Wire or High Leg D.
back to List of alarms level 2
Alarm Type
Breaker open
Alarmlist message
No
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
This alarm evaluates the Bus Left phase voltage in phases. The following setpoints
are related to it:
Bus Left Overvoltage (page 188)
Bus Left < > Voltage Delay (page 189)
Note:
Alarm is active only in case the setpoint
is
set to 3Ph4Wire.
Bus Left L2 Overvoltage
back to List of alarms level 2
Alarm Type
Breaker open
Alarmlist message
No
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
This alarm evaluates the Bus Left phase voltage in phases. The following setpoints
are related to it:
Bus Left Undervoltage (page 188)
Bus Left < > Voltage Delay (page 189)
Note:
Alarm is active only in case the setpoint
is
set to 3Ph4Wire.
Bus Left L2 Undervoltage
back to List of alarms level 2
Alarm Type
Breaker open
Alarmlist message
No
Alarm evaluated
All the time
Bus Left L2L3 Overvoltage