InteliMains 210 Global Guide
188
Setpoint group
Bus Left Settings
Related FW
2.0.0
Range [units]
1 .. 200 [%] of
Default value
50 %
Alternative config
NO
Step
1 % of
Comm object
8284
Related applications
MCB, MGCB, BTB
Description
Threshold for Bus Left current asymmetry (unbalance).
Current Unbalance
Setpoint group
Bus Left Settings
Related FW
2.0.0
Range [units]
0,0 .. 600,0 [s]
Default value
5,0 s
Alternative config
NO
Step
0,1 s
Comm object
8285
Related applications
MCB, MGCB, BTB
Description
Delay for
protection.
Current Unbalance Delay
Subgroup: Bus Left Voltage Limits
Setpoint group
Bus Left Settings
Related FW
2.0.0
Range [units]
Bus Left Undervoltage (page 188)
.. 150 [%]
Default value
110 %
Alternative config
NO
Step
1 % of
Nominal Voltage Ph-Ph (page 177)
Comm object
8305
Related applications
MCB, MGCB, BTB
Description
Threshold for Bus Left overvoltage. All three phases are checked. Maximum out of three is used.
Bus Left Overvoltage
Setpoint group
Bus Left Settings
Related FW
2.0.0
Range [units]
50 ..
Bus Left Overvoltage (page 188)
[%]
Default value
60 %
Alternative config
YES
Step
1 % of
Nominal Voltage Ph-Ph (page 177)
Comm object
8307
Related applications
MCB, MGCB, BTB
Description
Threshold for Bus Left undervoltage. All three phases are checked. Minimum voltage out of three phases is
used.
Bus Left Undervoltage