InteliMains 210 Global Guide
175
Group: Basic settings
Subgroup: Name
Setpoint group
Basic settings
Related FW
2.0.0
Range [units]
0 .. 15 characters [-]
Default value
InteliGen
Alternative config
NO
Step
[-]
Comm object
8637
Related applications
MCB, MGCB, BTB
Description
User defined name, used for the controller identification at remote phone or mobile connection. Gen-Set
Name is maximally 15 characters long and can be entered using InteliConfig or from controller’s
configuration menu.
Note:
If the Gen-Set Name is "TurboRunHours", the running hours will be counted faster - 1 minute in
real will represent 1 hour.
Controller Name
Subgroup: Power settings
Setpoint group
Basic settings
Related FW
2.0.0
Range [units]
1 .. 5 000 [kW]
Default value
200 kW
Alternative config
Yes
Step
1 kW
Comm object
8276
Related applications
MCB, MGCB, BTB
Description
Nominal power imported from the Bus. Bus Overload BOR protection is based on this setpoint.
Nominal Bus Import
Subgroup: Current settings
Setpoint group
Basic settings
Related FW
2.0.0
Range [units]
1 .. 10 000 [A]
Default value
350 A
Alternative config
YES
Step
1 A
Comm object
8275
Related applications
MCB, MGCB, BTB
Description
It is current limit for current protections and means maximal continuous current.
Note:
To lock this setpoint against editing you also have to lock setpoint
,
and
Nominal Current