InteliMains 210 Global Guide
511
Alarm Type
Warning
Alarmlist message
Wrn BadPwrCfg
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
This alarm is issued when there is different power format on controller which are
connected via CAN2.
Wrn BadPwrCfg
back to List of alarms level 1
Alarm Type
Warning
Alarmlist message
Wrn + Name of binary input
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
Binary input also can be adjusted like alarm. In this case message in alarmlist
contains prefix - Wrn and binary input name. This alarm occurs, when appropriate
binary input is active.
Wrn BIN Protection
back to List of alarms level 1
Alarm Type
Warning
Alarmlist message
Wrn MCB Fail
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
This alarm will occur when the
input does not match
the expected position given by the
output. It stays
active until the mismatch between the output and feedback disappears.
If there was no command issued by the controller and the breaker
(feedback) changes suddenly the position itself, the alarm will be issued
immediately.
The alarm will be also issued, if the breaker does not respond to the close
command within 2 seconds. After this period has elapsed the output
is deactivated again and the next attempt to close
the breaker will occur first after the alarm is reset.
Wrn BTB Fail