InteliMains 210 Global Guide
502
Group: Other functions
PLC group
Other functions
Related FW
2.0.0
Related applications
AMF, MRS MINT, SPtM
Comm object
9
Inputs
Input
Type
Negation
Range
Function
Input
Binary
No
0/1
A record with configured text is
recorded into the controller history
when the input is activated.
Outputs
No outputs.
Description
This block writes a record with defined text into the history when the input is activated.
Image 8.154 Configuration of Force Hist block
Note:
Maximal number of characters for history message is 15.
Force History Record
PLC group
Other functions
Related FW
2.0.0
Related applications
AMF, MRS MINT, SPtM
Comm object
10
Inputs
Input
Type
Negation
Range
Function
Lvl 1
Binary
No
0/1
The input activates yellow level of the
configured protection if it is configured
Lvl 2
Binary
No
0/1
The input activates red level of the
configured protection if a red level
protection is configured
Fls
Binary
No
0/1
The input activates sensor fail if a fls
protection is configured
Force Protection