InteliMains 210 Global Guide
204
Group: Synchronisation
Setpoint group
Synchronisation
Related FW
2.0.0
Range [units]
Phase Match / Slip Synchro [-]
Default value
Phase Match
Alternative config
NO
Step
[-]
Comm object
14802
Related applications
MCB, MGCB, BTB
Description
This setpoint adjusts the type of synchronization.
Phase Match
This type of synchronization is based on voltage and phase shift match. Limits are
adjusted via setpoints
and
When voltage and phase shift are match,
starts countdown.
After that the command for breaker closing is activated.
Slip Synchro
This type of synchronization regulates the value of frequency to the value Mains/Bus
fre
(Mains frequency in SPtM, Bus frequency in
MINT application). When this frequency is reached,
starts
countdown. After that the command for breaker closing is activated. The closing
breaker command is issued in advance due to latency of breakers (adjusted via
setpoints
and
).
Note:
Condition of
has to be also fulfilled.
Synchronization Type
Setpoint group
Synchronisation
Related FW
2.0.0
Range [units]
OFF / 1 .. 1800 [s]
Default value
60 s
Alternative config
NO
Step
1 s
Comm object
8657
Related applications
MCB, MGCB, BTB
Description
This setpoint adjusts the maximum duration of synchronizing.
Note:
If this setpoint is adjusted to OFF then automatic restart of synchronization occurs every 180s.
This method helps to synchronize successfully even in difficult conditions.
Synchronization Timeout