Group: Bus Left Settings
Subgroup: Overload Protection
Setpoint group
Bus Left Settings
Related FW
2.0.0
Range [units]
0 .. 200 [%]
Default value
120 %
Alternative config
NO
Step
1 % of
Comm object
8280
Related applications
MCB, MGCB, BTB
Description
Threshold level for Bus Left overload (in % of Nominal power) protection. Protection is BOR.
Overload BOR
Setpoint group
Bus Left Settings
Related FW
2.0.0
Range [units]
0 .. 200 [%]
Default value
120 %
Alternative config
NO
Step
1 % of
Comm object
9685
Related applications
MCB, MGCB, BTB
Description
Threshold level for Bus Left overload (in % of Nominal power) protection. This is only warning.
Overload Wrn
Setpoint group
Bus Left Settings
Related FW
2.0.0
Range [units]
0,0 .. 600,0 [s]
Default value
5,0 s
Alternative config
NO
Step
0,1 s
Comm object
8281
Related applications
MCB, MGCB, BTB
Description
Delay for
and
protection.
Overload Delay