InteliLite Global Guide
339
Setpoint group
EM-BIO8-EFCP
Related FW
1.2.1
Range [units]
0,03 .. 5,00 [s]
Default value
0,10 s
Alternative config
NO
Step
0,01 s
Comm object
11633
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Only if relevant module is installed
Description
Delay for Earth Fault Current protection.
Earth Fault Delay
Setpoint group
EM-BIO8-EFCP
Related FW
1.2.1
Range [units]
1 [A] / 5 [A]
Default value
5 A
Alternative config
NO
Step
[-]
Comm object
14340
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Only if relevant module is installed
Description
There are 2 physical inputs for
Earth Fault Current Protection (page 338)
. Value of this setpoint has to be set
on value of physical input which is presently in use.
Earth Fault CT Input Range
Setpoint group
EM-BIO8-EFCP
Related FW
1.2.1
Range [units]
1 .. 2000 [1/(1or5)A]
Default value
500 1/(1or5)A
Alternative config
NO
Step
1A/1A; 1A/5A
Comm object
14339
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Only if relevant module is installed
Description
Earth Fault current transformer ratio.
Note:
Type of units depends on setpoint
Earth Fault CT Input Range (page 339)
which have to be set
before this setpoint.
Earth Fault CT Ratio
Summary of Contents for InteliLite MRS16
Page 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Page 55: ...InteliLite Global Guide 55 ...
Page 56: ...InteliLite Global Guide 56 ...
Page 57: ...InteliLite Global Guide 57 ...
Page 58: ...InteliLite Global Guide 58 ...
Page 59: ...InteliLite Global Guide 59 ...
Page 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Page 61: ...InteliLite Global Guide 61 History Log ...
Page 62: ...InteliLite Global Guide 62 ...
Page 63: ...InteliLite Global Guide 63 ...
Page 64: ...InteliLite Global Guide 64 ...
Page 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Page 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Page 67: ...InteliLite Global Guide 67 Change password ...
Page 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Page 69: ...InteliLite Global Guide 69 Log out from controller ...
Page 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Page 72: ...InteliLite Global Guide 72 ...
Page 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Page 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Page 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...