InteliLite 9 Global Guide
192
Group: Generator settings
Subgroup: Overload Protection
Setpoint group
Generator settings
Related FW
1.1.0
Range [units]
.. 200 [%]
Default value
120 %
Alternative config
NO
Step
1 % of
Comm object
8280
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold level for generator overload (in % of Nominal power) protection. Protection is BOC (Breaker Open
and gen-set Cooldown).
Note:
When there is no control of breakers, the type of protection is Sd not BOC.
Overload BOC
Setpoint group
Generator settings
Related FW
1.1.0
Range [units]
0 ..
[%]
Default value
120 %
Alternative config
NO
Step
1 % of
Comm object
9685
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold level for generator overload (in % of Nominal power) protection. This is only warning.
Overload Wrn
Setpoint group
Generator settings
Related FW
1.1.0
Range [units]
0,0 .. 600,0 [s]
Default value
5,0 s
Alternative config
NO
Step
0,1 s
Comm object
8281
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Delay for
Overload BOC (page 192)Overload BOC (page 192)
and
protection.
Overload Delay